![PV Powered StarInverter PVP1100 Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/pv-powered/starinverter-pvp1100/starinverter-pvp1100_installation-and-operation-manual_1628548027.webp)
PV Powered LLC
26
11-18-28-704
5.0 SPECIFICATIONS
Specifications
PVP1100
PVP1800
PVP2800
Maximum System Voltage
180VDC 360VDC 450VDC
Operating DC Voltage
Range
90-180VDC 120-360VDC
208: 180VDC-390VDC
240: 200VDC-390VDC
Maximum DC Operating
Current
14A 15A 15A
Maximum Array Short
Circuit Current (DC)
15A 15A 15A
Operating AC Voltage
Range
106V-132V 106V-132V
208: 183V-229V
240: 211V-264V
Operating Frequency
Range
59.3Hz-60.5Hz 59.3Hz-60.5Hz 59.3Hz-60.5Hz
Nominal AC Output
Voltage
120V
120V
208V or 240V
Normal Output Frequency
60Hz 60Hz 60Hz
Maximum Continuous
Output AC Current
11.5A 15A 14A
Maximum Output Fault
Current (AC)
15A 15A 15A
Output Overcurrent
Protection
15A 20A 20A
Peak Output Power
1100W 1800W 2800W
Peak Efficiency at @ 40
°
C
Ambient Temperature
95% 95% 97.6%
Enclosure
Aluminum-NEMA 3R to UL
50 Standards
Aluminum-NEMA 3R to UL
50 Standards
Aluminum-NEMA 3R to UL
50 Standards
Dimensions (WxDxH)
13.1” x 6.5” x 19.75”
(with optional AC DC
Disconnect-13.1” x 6.5” x
26.75”)
13.1” x 6.5” x 19.75”
15” x 7.5” x 21.75”
Weight
38lbs 46lbs 74lbs
Cooling
Natural Convection
Natural Convection
Natural Convection
Relative Humidity
0% to 100% Condensing
0% to 100% Condensing
0% to 100% Condensing
Ambient Temperature
Range
-25
°
C to +40
°
C -25
°
C to +40
°
C -25
°
C to +40
°
C
Environmental Rating
Conformal Coating per UL
Standards
Conformal Coating per UL
Standards
Conformal Coating per UL
Standards
Listings
UL 1741, IEEE 519, IEEE
929, NEC 690
UL 1741, IEEE 519, IEEE
929, NEC 690
UL 1741, IEEE 519, IEEE
929, NEC 690