4.0 TROUBLESHOOTING
If the StarInverter’s “STAND BY” LED remains red for a prolonged period (longer than the
5 minute timer required by code), and all of the operating parameters are within
specification (see system specifications), the AC breaker or AC disconnect should be
turned to the OFF position for 1 minute and then returned to the ON position. If the DC
and AC voltage levels are within specification, the red “STAND BY” LED will not be
illuminated. The green “OK” LED will be illuminated and the inverter will produce power
after 5 minutes. If the red “STAND BY” light remains illuminated, double-check all
connections and voltage levels. If the red “STAND BY” light is still illuminated, contact
your authorized dealer/distributor for product support.
In addition to the above fault indicators, the PVP Command Center software will indicate
system status. If a fault has occurred, a fault message as well as the corresponding code
will be displayed.
The vacuum fluorescent display (models PVP1800 and PVP2800) will provide the following
codes when a fault has occurred:
First Code:
PDPA FAULT
0x8000
power module generated fault
VOLTAGE FAULT
0x1000
Code 3 will contain further information
GROUND FAULT
0x0400
LOW POWER FAULT
0x0200
array power too low for max power
tracking
CPU LOAD FAULT
0x0100 software
overload
OVERCURRENT FAULT
0x0040
PRECHARGE FAULT
0x0020
HEATSINK TEMP FAULT
0x0004
AMBIENT TEMP FAULT
0x0001
Second Code:
0x0000
will always remain zero
Third Code: (Voltage Faults)
PLL
FAULT
0x0400
AC voltage sensing missing per UL
AC OVERVOLTAGE FAULT
0x0200
AC UNDERVOLTAGE FAULT
0x0100
AC FREQUENCY FAULT
0x0080
DC UNDERVOLTAGE FAULT
0x0020
array voltage too low
DC OVERVOLTAGE FAULT
0x0010
P15
FAULT
0x0002
+15V supply out of specifications
PS
FAULT
0x0001
+5V supply out of specifications
As indicated above, there are three 16-bit codes assigned to describe faults, one of which
will always remain zero. More than one fault can be represented at a time. This will be
indicated by a fault with a code equal to the sum of the individual faults.