5
HYBRID M1 | Filtration & Ultraviolet All-in-One Undersink Unit
Installation Guide
Installation Requirements
•
Cold water line only.
•
Power supply: AC 240V | 50Hz
•
Supply pressure: 300-875 kPa. Install pressure limiting valve if pressure exceeds
500 kPa.
Note: For point of entry installations an approved dual check backflow
prevention device must be installed.
•
Supply temperature 0° - 52°C (protect from freezing).
•
Alternative fittings may be required if being connected to anything other than
15 mm threads.
Note: Only use thread seal tape. Do not use liquid sealant.
•
Ensure the water supply flow rate does not exceed the rated maximum of the
Hybrid system.
•
Ensure the electrical power supply to the Hybrid system is sufficient, allowing for
other appliances that may be connected to the circuit and ensuring it is surge
protected. If in doubt, please consult a qualified electrician.
•
Where the water being treated contains unusually high levels of dissolved solids
particularly hard water, iron, manganese or biological organisms, a deposit build up
on the quartz sleeve may occur over time. Maximum recommended parameters are
as follows:
Iron:
less than 0.3 mg/L
Hydrogen Sulfide:
less than 0.05 mg/L
Suspended Solids:
less than 10mg/L
Manganese:
less than 0.05 mg/L
Hardness:
less than 110mg/L
• Caution: Do not use with water that is microbiologically unsafe or of unknown
quality without adequate treatment before or after the system.
Application warning: minimum water characteristics must be met before
installation of Radfire™ to ensure proper operation and continuous protection.