Install mounting angle as shown in Fig. 3, using No. 8 self-
drilling screws provided. Remove a ceiling tile centrally 
located in area to be cleaned. Secure eyebolts, hooks etc. to 
permanent ceiling or ceiling joists. Determine length of 
chain necessary to support unit at maintaining angle or 
slightly above level of T-Bar frame. 
 

 
 

CAUTION: Do not allow full weight of unit to rest on T-Bar ceiling or frame. 

Attach proper length of chain to each eyebolt on cabinet, 

raise unit and secure chain to mounting devices in 
permanent ceiling or joists. (see Fig. 4)  

Connect electrical power to air cleaner, following 

instructions under 

“Electrical Wiring”.

 

Remove charcoal filter from plastic bag and install in 

channel on down-stream side of cell. (Arrow on side of 
cell points in this direction.)  Re-install cell, pre-filters and carbon filter. Swing access cover up 
and snap closed. Unit is now ready to place in operation. 

FLUSH MOUNT INSTALLATION 

Open unit cover and remove the pre-filter and cell. Select a 
location near the center of the area to be cleaned and locate 
the ceiling joists in that area. Locate 4 mounting points (each 
being at a joist) and pre-drill holes into the joists and unit 
housing as shown in Fig. 5. 

Lift unit into ceiling and secure using four ¼” x 2

- ½

” lag bolts 

as shown in Fig. 5. Connect electrical power to unit. (See Field 
Wiring Diagram) Remove carbon filter from plastic bag and 
install in guide rails on back of cell. Re-install cell, pre-filter and 
carbon filter. Replace thumb screws to secure cell in position. 
Close access cover and snap closed. Unit is ready for 
operation. 