Steam Supply Piping Examples 

Pitched Towards Steam Generator 

Pitched Towards Steam Generator  

and Tube Assembly 

1/4”/1’ 

2”/1’ 

Pitch 

(see Note 1) 

2”/1’ 

Notes: 

 

1.  Pitch hard piping or flexible hose 2" per foot if steam is flowing uphill, 1/4" per foot if the steam is flowing                      

downhill. Reference piping examples shown. 

2.  When feasible to do so, install a minimum one-foot riser from the top of the tank to reduce condensate carryover. 

3.  Use flex connectors or unions to allow for easy removal of cover. 

4.  Support flexible hose every 18" to avoid sagging. 

5.  Hard piping or flexible hose must match reservoir outlet size.  Do not use supply piping with a smaller inside diameter 

than the reservoir outlet. 

6.  Failure to follow the piping recommendation on this page may result in blown water seals, leaking cover gasket, or 

dispersion tubes spitting. 

7.  Install a Drain Tee at any low spots in supply piping run where condensate will accumulate.  

All

 

horizontal to vertical 

up transitions require a water-sealed drip leg.

 

8.  Reference job specific tube assembly O&M included with your order for complete details. 

Pitched Towards Tube Assembly 

Pitched Towards Drain Tee 

Drain Tee 

(see Note 7) 

1/4”/1’ 

2”/1’ 

1/4”/1’ 

Use two 45° elbows for  

hard piping or wide 90° for  

flexible steam hose 

Supply piping 

connectors 

(see Note 4) 

see Note 2 

Typical 

Humidifier 

Reservoir 

see Note 2 

see Note 2 

see Note 2 

Содержание Fast-Pac

Страница 1: ...have to be increased ES EC Water Seal Height if excessive duct static pressure exists 11 28 cm 8 20 cm 17 43 cm 19 48 cm 58 5 thru 102 Total KW 22 thru 33 3 thru 19 5 39 thru 49 5 151 and above 100 t...

Страница 2: ...iameter Duct plates are provided to seal the opening The layout should be based on the Location instructions listed above see Fig 3 2 Cut a hole through the AHU or duct wall for the supply connection...

Страница 3: ...rt bracket 1 6 Tube mounting bolts 1 per tube 7 Duct plate condensate 1 ITEM NO DESCRIPTION QUANTITY Header drain connection 3 4 NPT Fig 2 4 1 Header mounting bracket welded onto the header 7 Steam in...

Страница 4: ...on tubes with the orifices injecting upwards 4 All condensate drain piping is by others Header Support Bracket Mounting Detail Fig 3 Condensate drain connection dashed line is the alternate location s...

Страница 5: ...locity of 300 feet per minute is required to avoid saturation and excessive fog travel Controls Fan Interlock Switch PURE Humidifier Co recommends the use of an air flow proving switch or fan interloc...

Страница 6: ...Little Humidity 1 Humidity controller out of calibration 2 Undersized humidifier 3 Check humidifier GX SX ES EC for proper operation 4 Water seals are not primed 5 Water seals are blown due to imprope...

Страница 7: ...h reservoir outlet size Do not use supply piping with a smaller inside diameter than the reservoir outlet 6 Failure to follow the piping recommendation on this page may result in blown water seals lea...

Страница 8: ...oducts The Seller reserves the right to make reasonable changes in products specifications and performance of any kind without notice or liability The Seller also reserves the right to deliver revised...

Отзывы: