Installation Tips 

 

Condensate Return Line 

Condensate from the header cannot be elevated.  Do not connect water seals to  

pressurized condensate return lines.  

The drain piping should be copper or stainless 

steel.  The use of PVC piping is not recommended; the humidifier temperature will 

cause the PVC to soften and fail. 

 
 

Laminar air flow 

Tube assembly must be installed in a location that allows for laminar air flow across entire 
grid.  A minimum velocity of 300 feet per minute is required to avoid saturation and 
excessive fog travel. 
 

Plug fan installations 

Install tube assembly as close as possible to the upstream coil to ensure laminar airflow and 
proper absorption.  

 
Insulated ducts 

Internally insulated ducts must be lined with a non-absorbent material to avoid saturation.  If 
the duct is lined it must be removed three feet (3’) upstream and ten feet (10’) downstream 
of tube assembly. 
  

Final Filters 

Tube assembly must be installed a minimum of ten feet (10’) upstream of final filters. 
 

VAV Systems 

Low velocity will cause long fog trails and steam will rise wetting the top of the AHU/duct 
casing.  Modulating VAV high-limit humidistat is required.  A minimum velocity of 300 feet 
per minute is required to avoid saturation and excessive fog travel. 
 
 

Controls 

 

Fan Interlock Switch 

PURE Humidifier Co. recommends the use of an air flow proving switch or fan interlock to 
prove air flow prior to humidifier cooperation.  Humidifier operation without air flow will result 
in over-saturation of the air stream.  Air flow proving switches are available as optional 
equipment from your PURE Humidifier Co. representative. 
 

High-Limit Humidistat 

PURE Humidifier Co. recommends the use of a duct high-limit humidistat to prevent 
humidifier operation when the duct humidity level exceeds 85% relative humidity.  Humidifier 
operation above 85% relative humidity can result in over-saturation of the air stream.  High-
limit humidistats are available as optional equipment from your PURE Humidifier Co. 
representative.  The high limit humidistat should be 8 to 10 feet (244-305 cm) downstream 
from the humidifier injection tube.  Installing the high-limit closer than 8 feet (244 cm) from 
the humidifier may cause erratic control.

 

 
 

Smoke Alarms and Temperature Sensors 

Smoke alarms should be located 12 to 14 feet (365-427 cm) upstream from the humidifier 
injection tube. 
 
Temperature sensors should be located 12 to 14 feet (365-427 cm) downstream from the 
humidifier injection tube, or past any visible fog travel that may be greater than this distance

.

 

 
 

Содержание Fast-Pac

Страница 1: ...have to be increased ES EC Water Seal Height if excessive duct static pressure exists 11 28 cm 8 20 cm 17 43 cm 19 48 cm 58 5 thru 102 Total KW 22 thru 33 3 thru 19 5 39 thru 49 5 151 and above 100 t...

Страница 2: ...iameter Duct plates are provided to seal the opening The layout should be based on the Location instructions listed above see Fig 3 2 Cut a hole through the AHU or duct wall for the supply connection...

Страница 3: ...rt bracket 1 6 Tube mounting bolts 1 per tube 7 Duct plate condensate 1 ITEM NO DESCRIPTION QUANTITY Header drain connection 3 4 NPT Fig 2 4 1 Header mounting bracket welded onto the header 7 Steam in...

Страница 4: ...on tubes with the orifices injecting upwards 4 All condensate drain piping is by others Header Support Bracket Mounting Detail Fig 3 Condensate drain connection dashed line is the alternate location s...

Страница 5: ...locity of 300 feet per minute is required to avoid saturation and excessive fog travel Controls Fan Interlock Switch PURE Humidifier Co recommends the use of an air flow proving switch or fan interloc...

Страница 6: ...Little Humidity 1 Humidity controller out of calibration 2 Undersized humidifier 3 Check humidifier GX SX ES EC for proper operation 4 Water seals are not primed 5 Water seals are blown due to imprope...

Страница 7: ...h reservoir outlet size Do not use supply piping with a smaller inside diameter than the reservoir outlet 6 Failure to follow the piping recommendation on this page may result in blown water seals lea...

Страница 8: ...oducts The Seller reserves the right to make reasonable changes in products specifications and performance of any kind without notice or liability The Seller also reserves the right to deliver revised...

Отзывы: