Notes: 
 
1.)  Center the Fast-Pac injection tube assembly in the duct height. 
 
2.)  The injection tubes should pitch back towards the header with a minimum 
 

of 2" per foot of pitch (see above illustration). 

 
3.)  Install injection tubes with the orifices injecting upwards. 
 
4.)  All condensate drain piping is by others. 
 

Header & Support Bracket Mounting Detail 

Fig. 3 

Condensate drain connection

(dashed line is the alternate

location - special order)

Cut openings for
supply and drain

connections.

Seal with duct plates

Injection tube

Steam

supply

inlet(s)

2" Pitch per foot

End bracket
mounting bolts

AHU casing or duct wall

Supply/

condensate

header

Содержание Fast-Pac

Страница 1: ...have to be increased ES EC Water Seal Height if excessive duct static pressure exists 11 28 cm 8 20 cm 17 43 cm 19 48 cm 58 5 thru 102 Total KW 22 thru 33 3 thru 19 5 39 thru 49 5 151 and above 100 t...

Страница 2: ...iameter Duct plates are provided to seal the opening The layout should be based on the Location instructions listed above see Fig 3 2 Cut a hole through the AHU or duct wall for the supply connection...

Страница 3: ...rt bracket 1 6 Tube mounting bolts 1 per tube 7 Duct plate condensate 1 ITEM NO DESCRIPTION QUANTITY Header drain connection 3 4 NPT Fig 2 4 1 Header mounting bracket welded onto the header 7 Steam in...

Страница 4: ...on tubes with the orifices injecting upwards 4 All condensate drain piping is by others Header Support Bracket Mounting Detail Fig 3 Condensate drain connection dashed line is the alternate location s...

Страница 5: ...locity of 300 feet per minute is required to avoid saturation and excessive fog travel Controls Fan Interlock Switch PURE Humidifier Co recommends the use of an air flow proving switch or fan interloc...

Страница 6: ...Little Humidity 1 Humidity controller out of calibration 2 Undersized humidifier 3 Check humidifier GX SX ES EC for proper operation 4 Water seals are not primed 5 Water seals are blown due to imprope...

Страница 7: ...h reservoir outlet size Do not use supply piping with a smaller inside diameter than the reservoir outlet 6 Failure to follow the piping recommendation on this page may result in blown water seals lea...

Страница 8: ...oducts The Seller reserves the right to make reasonable changes in products specifications and performance of any kind without notice or liability The Seller also reserves the right to deliver revised...