2.0 APPLIANCE DATA
4
Model
Country of
Destination
Cat
Gas Type
Operating Pressure
(±2.0 mbar)
Max Energy Input (kW) Min Energy Input (kW)
G20 G25 G30 G31
Gross
Net
Gross
Net
All P23 models
GB - IE
I2H
Natural
20
-
-
-
2.0
1.8
1.0
0.9
All L23 models
GB - IE
I2H
Natural
20
-
-
-
2.0
1.8
1.3
1.15
GB IE
©
2012 Pure Glow Limited
Flow Restrictor Orifice - All Models
Size 1.00
Oxypilot - All Models
SIT 9082
Gas Control - All Models
Copreci 21400/342
Gas Inlet - All Models
8mm
Ignition - All Models
Piezo Spark
Spark Gap - All Models
3.5 - 4.5mm
Please see Data Badge affixed to appliance for current data.
This appliance is for use only with the gas type, and at the pressure stated on the appliance Data Badge.
3.0 INSTALLATION REQUIREMENTS
If the appliance is to be sited near a disused or unserviceable fireplace served by a natural draught flue then the old flue must be
sealed off. It will be necessary to ventilate the old flue to prevent condensation and dampness forming, however any air vent used to
ventilate the old flue must not be sited within 500mm of this appliance. If the flue can be ventilated to the outside of the building
then this is usually the best solution. If in doubt then advice should be sought from a local building control officer. The appliance is
designed to be wall mounted. If the appliance is to be mounted on a newly fabricated area of wall that also serves the purpose of
sealing off the old flue then it is very important that there are no holes, gaps or otherwise in this wall that will allow draughts from
the old flue to enter the room, especially directly behind the appliance. Such draughts could affect the performance of the ODS sys-
tem and result in nuisance cutting out, for example. If the gas supply pipe is to enter the appliance from the rear, i.e. emerge from
the wall behind the appliance, then any hole in the wall from which the pipe emerges must be tightly sealed.
All Models : The room size MUST be a minimum of 23m
3
(e.g. 10’1” x 10’1” x 8’) to allow adequate circulation of air and
ensure the correct operation of the fire. This volume may include adjacent spaces but these spaces must not be separated by a
door. To calculate a room size in cubic metres (m
3
) divide the room volume in cubic feet (ft
3
) by 35.3.
This appliance may be installed in any room in the home except bathrooms or bedrooms.
The appliance is designed to be versatile, and as such will operate correctly when exposed
to normal gentle draughts experienced within the home. It is not recommended, however
that the appliance be installed in areas where it is likely to be directly exposed to persistent
strong draughts, that may be generated by outside doors, windows, air vents, air condition-
ing units, extractor fans, ceiling fans etc. See section 4.1 for more information on ventilation.
Clearances to non-combustible materials
Non combustible surfaces are defined as brick, metal, marble, concrete etc. and also a number of man-made materials impervious
to flame. If in doubt refer to the material manufacturer for further information before proceeding with installation.
Clearances to the sides of the appliance are 100mm (4”). Clearance to the front of the appliance is 500mm (20”).
The back of the appliance may be installed directly onto a non-combustible wall, providing the area behind the appliance is flat
and does not interfere with the various vent holes in the back panel of the appliance.
A non combustible shelf of any depth may be positioned above the appliance provided it is no closer than 400mm (16”) from the
top of the appliance glass panel and the wall above the appliance is non combustible. The appliance must not be positioned ver-
tically within 60mm (2.4”) of a solid floor (i.e. wood or stone) or hearth. This dimension is measured vertically to the bottom of
the appliance firebox.
Clearances to combustible materials
Combustible materials are defined as wood, fabrics, or other materials likely to combust if exposed to flame. Generally, any mate-
rial, which is likely to discolour, melt or misshape when exposed to moderate heat, should be considered as a combustible mate-
rial or surface. Clearance to the sides of the appliance are 100mm (4”) but curtains, drapes and other fabrics are not permitted
within a distance of 500mm (20”) of the appliance sides. No such materials are permitted directly above the appliance regardless
of distance.
3.1 ROOM SIZING
4.0 SITE REQUIREMENTS
This appliance is designed to be
wall-hung. Do not recess any part
of the appliance into the wall.
WARNING