Page
90
P1-P102, P2-P1102 Material
This parameter should be set to the type of site being monitored for Sludge or the
material being monitored with air transducers. The options are:
VT transducers
Option
Description
1 = Industrial
Use for the majority of non-sludge sites
2 = Primary (Default)
Use for primary settlement tanks
3 = Secondary
Use for secondary settlement tanks
4 = SBR
Use for SBR tanks
dB transducers
Option
Description
1 = Liquid (Default)
Use for liquids and flat solid materials
2 = Solid
Solid material that is heaped or at an angle
P1-P105, P2-P1105 Empty Level (db transducers only)
This parameter is to be set to the
maximum distance
from the
face
of a dB
transducer to the
empty point
(bottom of the tank), in
P104
Measurement
Units
.
Note this value also affects span, (see important information below), so should be
set before span. With sludge transducers, the empty level is automatically
calculated from
P115 Tank Depth
and
P116 Transducer Depth
.
Содержание SLUDGE FINDER 2
Страница 1: ...SLUDGE FINDER 2 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 13: ...Page 7 EC Declaration of Conformity ...
Страница 14: ...Page 8 This page left blank intentionally ...
Страница 18: ...Page 12 The full dimensions of the enclosure are as shown below ...
Страница 25: ...Page 19 ...
Страница 29: ...Page 23 Transducer Installation Options 1 Stainless steel mounting plate Fig 1 ...
Страница 42: ...Page 36 Enclosure Dimensions ...
Страница 45: ...Page 39 Receiver and Transmitter Dimensional Details ...
Страница 70: ...Page 64 This page left blank intentionally ...
Страница 75: ...Page 69 Example Echo Screen for Ultrasonic Transducer Empty Distance Indicator Status Indicator ...
Страница 94: ...Page 88 This page left blank intentionally ...
Страница 132: ...Page 126 This page is left blank intentionally ...