Page
68
To program the unit for
Example2 Level Monitoring with alarms
, proceed as
follows.
If required access the
Program Mode
Key in the
passcode
1997
and press
ENTER
Use the arrow keys to scroll to the following menus and parameters and press
ENTER
to access them. Select the relevant option using the up and down arrows
or type in the required value using the keypad and press
ENTER
to accept.
Menu
Sub Menu
Parameter
Value/Option
Application
Point 2
Mode P1100
2 = Level
Xducer P1101
2 = dB6
Material P1102
1 = Liquid
Empty Level P1105
3.5 (metres)
Span P1106
2.8 (metres)
Relays
Relay 2
Type P220
1 = Alarm
Function P221
1 = Level
Ident P222
2 = High
Setpoint 1 P223
2.38 (metres)
Setpoint 2 P224
2.24 (metres)
Allocation P226
2 = Xducer 2
Relay 3
Type P230
1 = Alarm
Function P231
1 = Level
Ident P232
2 = Low
Setpoint 1 P233
0.28 (metres)
Setpoint 2 P234
0.42 (metres)
Allocation P236
2 = Xducer 2
mA Output
mAOut 2
Allocation P899
2 = Xducer 2
All other parameters should remain at default values.
Programming is now complete and the unit can be returned to the run mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the
Sludge Finder 2
will return to the
Run Mode
.
Содержание SLUDGE FINDER 2
Страница 1: ...SLUDGE FINDER 2 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 13: ...Page 7 EC Declaration of Conformity ...
Страница 14: ...Page 8 This page left blank intentionally ...
Страница 18: ...Page 12 The full dimensions of the enclosure are as shown below ...
Страница 25: ...Page 19 ...
Страница 29: ...Page 23 Transducer Installation Options 1 Stainless steel mounting plate Fig 1 ...
Страница 42: ...Page 36 Enclosure Dimensions ...
Страница 45: ...Page 39 Receiver and Transmitter Dimensional Details ...
Страница 70: ...Page 64 This page left blank intentionally ...
Страница 75: ...Page 69 Example Echo Screen for Ultrasonic Transducer Empty Distance Indicator Status Indicator ...
Страница 94: ...Page 88 This page left blank intentionally ...
Страница 132: ...Page 126 This page is left blank intentionally ...