Page 111
P1-P860, P2-P1860 Sound Velocity
This parameter allows for the velocity of sound to be changed according to the
atmosphere the transducer is operating in. By default the velocity is set for sound
travelling in air/water at an ambient temperature of 20 degrees centigrade.
Default = 342.72m/s (velocity in air for dB transducer)
Default = 1482.32m/s (velocity in water for VT transducer)
Stability Parameters
Point 1 / Point 2
Damping
Damping is used to damp the display, to enable it to keep up with the process but
ignore minor surface fluctuations.
P1-P870, P2-P1870 Fill Damping
This parameter determines the
maximum rate
at which the unit will respond to
an
increase in level
. It should be set slightly higher than the maximum vessel fill
rate.
Default = 10m/min
P1-P871, P2-P1871 Empty Damping
This parameter determines the
maximum rate
at which the unit will respond to a
decrease in level
. It should be set slightly higher than the maximum vessel empty
rate.
Default = 10m/min
Filters
The following two parameters can be used to filter out unwanted changes of level
caused by a ‘rippled’ or agitated surface.
P1-P881, P2-P1881 Fixed Distance
This parameter determines the width of gate to be used in tracking an echo and
under normal circumstances will not require changing, but it can be increased in
the cases where the surface is moving extremely fast (in excess of 10m/min) to
ensure smooth processing of the changing level.
Содержание SLUDGE FINDER 2
Страница 1: ...SLUDGE FINDER 2 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 13: ...Page 7 EC Declaration of Conformity ...
Страница 14: ...Page 8 This page left blank intentionally ...
Страница 18: ...Page 12 The full dimensions of the enclosure are as shown below ...
Страница 25: ...Page 19 ...
Страница 29: ...Page 23 Transducer Installation Options 1 Stainless steel mounting plate Fig 1 ...
Страница 42: ...Page 36 Enclosure Dimensions ...
Страница 45: ...Page 39 Receiver and Transmitter Dimensional Details ...
Страница 70: ...Page 64 This page left blank intentionally ...
Страница 75: ...Page 69 Example Echo Screen for Ultrasonic Transducer Empty Distance Indicator Status Indicator ...
Страница 94: ...Page 88 This page left blank intentionally ...