Page
106
Failsafe
P1-P808, P2-P1808 Fail-safe Mode
By default, if a fail-safe condition occurs, then the display, relays and the mA
output are held at their last
known
values until a valid reading is obtained.
If required, then you can change this so that the unit goes to
high
(100% of span),
or
low
(empty) as follows:
Option
Description
1 = Known (Default)
Remain at the last
known
value
2 = High
Will fail to the
high
value (100% of Span).
3= Low
Will fail to the
low
value (empty)
See Also P218, P228, P238, P248, P258, P268 - Relay Fail-safe and P840/P898 mA Output Fail-safe
Important Information
In the event of a
fail-safe
condition occurring, the display, relays and mA
Output can be configured to fail to a condition which is independent of each
other. To set independent
Relay Failsafe
see
P218, 228, 238, 248, 258, 268
.
And for independent
mA Output Failsafe
see
P840/P898.
P1-P809, P2-P1809 Fail-safe Time
In the event of a fail-safe condition the fail safe timer determines the time before
fail-safe mode is activated.
Default = 2mins
If the timer activates, the unit goes into
fail-safe
, as determined by
P808/P1808
,(
Display
),
P218, 228, 238, 248, 258, 268
(
Relays
) and
P840/P898
(
mA Output
). When this happens, the display/mA output/relay state will take on
that of the relevant fail mode.
When a valid measurement is obtained then the display, relays and mA output will
be restored and the timer is reset.
Содержание SLUDGE FINDER 2
Страница 1: ...SLUDGE FINDER 2 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 13: ...Page 7 EC Declaration of Conformity ...
Страница 14: ...Page 8 This page left blank intentionally ...
Страница 18: ...Page 12 The full dimensions of the enclosure are as shown below ...
Страница 25: ...Page 19 ...
Страница 29: ...Page 23 Transducer Installation Options 1 Stainless steel mounting plate Fig 1 ...
Страница 42: ...Page 36 Enclosure Dimensions ...
Страница 45: ...Page 39 Receiver and Transmitter Dimensional Details ...
Страница 70: ...Page 64 This page left blank intentionally ...
Страница 75: ...Page 69 Example Echo Screen for Ultrasonic Transducer Empty Distance Indicator Status Indicator ...
Страница 94: ...Page 88 This page left blank intentionally ...
Страница 132: ...Page 126 This page is left blank intentionally ...