RSUPS98R
RACK POWER
8
3.2. Optical indication of the switch operation:
OPTICAL INDICATION OF THE SWITCH's POWER SUPPLY
GREEN LED LIGHT (Power)
Indication of the switch's power
supply
OFF
– no power supply of the switch
ON
– power supply on, normal operation
OPTICAL INDICATION OF THE SWITCH's POWER SUPPLY (1
÷8)
GREEN LED LIGHT (PoE)
Indication of the PoE power
supply at the RJ45 ports
OFF
- no power supply at the RJ45 port (the device is not connected or not compliant
with the IEEE802.3af standard)
ON
– supply at the RJ45 port
Blinking
– short-circuit or output overload
YELLOW LED LIGHT (LINK)
The connection status of LAN
devices, 10MB/s or 100Mb/s
and data transmission
OFF
- no connection
ON
- the device is connected; 10Mb/s or 100Mb/s
Blinking
– data transmission
OPTICAL INDICATION AT THE UPLINK PORT
GREEN LED LIGHT
OFF
- no connection
ON
– the device is connected; 10Mb/s or 100Mb/s
YELLOW LED LIGHT (LINK)
The connection status of LAN
devices, 10MB/s or 100Mb/s
and data transmission
OFF
- no data transmission
ON
- the device is connected: 10Mb/s or 100Mb/s
Blinking
– data transmission
3.3. Technical output.
The power supply is fitted with the
ALARM
output of collective failure (relay type). A collective failure can
be triggered by the following events:
- 230V AC mains power failure
- Failure of the switch mode power supply
- No voltage at the power supply output of the recorder
- Too high temperature of the switch mode power supply (>70
°C)
- Low battery voltage (<23V)
Fig. 5. Electrical diagram of the ALARM collective output of failure.
CAUTION!
In Fig.5 the set of contacts shows a potential-free status of the relay, which
corresponds to power supply failure.
3.4. Acoustic indication.
A collective failure is indicated by the piezoelectric indicator, 1 beep every second. The acoustic indication
can be turned off by changing the ON / OFF position of the switch .
switch in the up position, indication ON
switch in the down position, indication OFF