www.pulsar.pl
EN54-7A28
RED POWER
18
temperature
ALARM
- Overloaded batteries.
- Faulty batteries.
F16
No battery!
APS FLT,
ALARM
- Disconnected batteries
Section 7.1
F17
Faulty battery!
APS FLT,
ALARM
- Deeply discharged batteries , voltage below 20V
Section 7
F18
High resistance
of the. Battery
circuit!
APS FLT,
ALARM
- Spent batteries
- Loose cables connecting the batteries
Section 7.6
F19
High AC
voltage!
PSU FLT,
ALARM
- Mains supply over 254V AC
Section 6.2.5.
F20
Low AC voltage!
PSU FLT,
ALARM
- Mains supply below 195V AC
Section 6.2.5.
F21
Enclosure
opening!
PSU FLT,
ALARM
Section 6.6
F50-
F54
Internal damage
of the PSU.
PSU FLT,
ALARM
- service codes
F60
No
communication
PSU FLT,
ALARM
- no communication with LCD panel
F61-
F64
LCD damage
PSU FLT,
ALARM
- service codes
F65
Access
unlocked
- passwords unlocked
Table 9. List of PSU message codes.
Message
code
Description
I00
Running the PSU
I01
AC power restored
AUX1 fuse replaced
I02
AUX2 fuse replaced
I03
BAT fuse replaced
I04
Battery connected
I05
Battery OK
I06
Correct battery temperature
I07
Correct AC voltage
I08
EXTo output on
I09
EXTo output off
I10
Battery test – START
I11
PSU’s lid closed
I12
The Imax_a current exceeded
I13
The current has dropped below Imax_a