R1624T 

 

 

    

           

RACK POWER

 

 

3.  Operating status indication. 
 

3.1.  LED indication. 

The PSU has 20 LED lights at the front panel: 
 

 

 
 
 

 

 
 
 

 

 
 

 

 
 
 
 

 

 
 

GREEN LED: 

 

on – the PSU is supplied with 230V AC 

 

off – no 230V AC supply 

 

GREEN LED: 

 

on – DC voltage at the output of the switch mode PSU 

 

off – no DC voltage at the output of the switch mode PSU 

 
 

RED LED: 

 

on – failure 

 

off – no failure 

 

 
RED LED: 

 

ON – too high temperature of the switch mode power supply 
(>70°C) 

 

OFF – standard temperature of the switch mode power supply 

 

 

 
 

GREEN LED: 

 

on – DC voltage in the AUX1…AUX16 output 

 

off – no DC voltage in the AUX1…AUX16 output 

 

 

3.2.  Technical output. 

 
The power supply is fitted with the 

ALARM

 output of collective failure (relay type). A collective failure can 

be triggered by the following events: 

- 230V AC mains power failure 
- Melting fuse activation 

F1÷F16 

- Failure of the switch mode power supply 
- Too high temperature of the switch mode 

power supply (>70°C) 

 

 

 

Fig. 4. Electrical diagram of the ALARM collective output of failure. 

 

 

CAUTION!

  In  Fig.  4  the  set  of  contacts  shows  a  potential-free  status  of  the  relay,  which 

corresponds to power supply failure. 

 

 
 
 
 
 
 
 

 

Содержание R1624T

Страница 1: ...R1624T v 1 0 R 24V 16x0 5A TOPIC RACK mounted power supply EN Edition 1 from 22 09 2017 Supercedes the edition...

Страница 2: ...r loss activation of the output fuse in the camera power supply circuit too high temperature of the PSU 70 C the PSU failure protections SCP short circuit protection OVP overvoltage protection overvol...

Страница 3: ...unting in standard RACK 19 cabinets 1 2 Block diagram Fig 1 The block diagram of the PSU 1 3 Description of PSU components and connectors Table 1 Components of the front panel of the power supply Elem...

Страница 4: ...www pulsar pl R1624T RACK POWER 4 Fig 2 The front power of the power supply unit Fig 3 The view of the PSU...

Страница 5: ...s tab 3 Enclosure dimensions W 19 H 2U 482 x 88 x 223 mm WxHxD Fixation four point butt mounting to RACK profiles the set include 4 M6 screws cage nuts Net weight 5 4kg 5 9kg Enclosure Steel plate RAL...

Страница 6: ...rmed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before...

Страница 7: ...re of the switch mode power supply GREEN LED on DC voltage in the AUX1 AUX16 output off no DC voltage in the AUX1 AUX16 output 3 2 Technical output The power supply is fitted with the ALARM output of...

Страница 8: ...ed with a fuse of the same type 4 2 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require perfor...

Отзывы: