RACK POWER

 

 

2.  Installation. 
 

2.1.  Requirements. 

The PSU RACK shall be mounted by a qualified installer with appropriate permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without condensation) and the temperature from -

10°C do +45°C.  

 

     During normal operation the total current consumption of the receivers cannot exceed I=8A.  

      

As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations.  

 

2.2. Installation procedure. 

 

1. Before installation, cut off the voltage in the 230V power-supply circuit. 

2. Mount the power supply in a RACK 19" cabinet as shown below: 
 

 

- Mount M6 cage nuts 

 

- Secure the enclosure with 4xM6 screws 

 
3. Connect the 

receivers’ cables to the terminals AUX1...AUX16. 

4. If needed, the following technical connections can be made: 
- ALARM 

– technical output of collective failure 

5.  Connect  the  ~230V  AC  power  cord  with  the  IEC  C13  plug  (included)  to  the  230V  AC  power  supply  and  turn  on  the 
power (~230V). 
6. In the case of an unsafe voltage supply with  frequent voltage drops in effective resistance of receiver supply cables 
can occur, it is possible to adjust the output voltage using the potenti

ometer (20V÷26V DC) at the front panel of the power 

supply. 
7. Check the PSU operation indicator. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Содержание R1624T

Страница 1: ...R1624T v 1 0 R 24V 16x0 5A TOPIC RACK mounted power supply EN Edition 1 from 22 09 2017 Supercedes the edition...

Страница 2: ...r loss activation of the output fuse in the camera power supply circuit too high temperature of the PSU 70 C the PSU failure protections SCP short circuit protection OVP overvoltage protection overvol...

Страница 3: ...unting in standard RACK 19 cabinets 1 2 Block diagram Fig 1 The block diagram of the PSU 1 3 Description of PSU components and connectors Table 1 Components of the front panel of the power supply Elem...

Страница 4: ...www pulsar pl R1624T RACK POWER 4 Fig 2 The front power of the power supply unit Fig 3 The view of the PSU...

Страница 5: ...s tab 3 Enclosure dimensions W 19 H 2U 482 x 88 x 223 mm WxHxD Fixation four point butt mounting to RACK profiles the set include 4 M6 screws cage nuts Net weight 5 4kg 5 9kg Enclosure Steel plate RAL...

Страница 6: ...rmed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before...

Страница 7: ...re of the switch mode power supply GREEN LED on DC voltage in the AUX1 AUX16 output off no DC voltage in the AUX1 AUX16 output 3 2 Technical output The power supply is fitted with the ALARM output of...

Страница 8: ...ed with a fuse of the same type 4 2 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require perfor...