Pulsar R1624T Скачать руководство пользователя страница 5

www.pulsar.pl

    

 

 

 

R1624T 

 

 

    

           

RACK POWER

 

 

1.4.  Specifications. 

- electrical parameters (tab.2) 
- mechanical parameters (tab.3) 
- operation safety (tab.4) 
- operating parameters (tab.5) 

 Electrical parameters (tab. 2). 

Mains supply 

230V AC (-15%/+10%) 50Hz 

Current up to 

1A max./230V AC 

Supply power 

192W max. 

Efficiency 

82% 

Output voltage 

24V DC 

Voltage adjustment range output 

2

0÷26V DC 

Output current 

16 x 0,5A (



I = 8A) 

max. @24V

 

Ripple 

150 mV p-p max. 

Short-circuit protection SCP 

16 x F 0,5A melting fuse 

Overload protection OLP 

105% ÷ 150% of the PSU power, automatic return 

Overvoltage protection OVP 

29,5 ÷ 35V (PSU restart required) 

Surge protection 

varistors 

Optical indication of operation: 

LED: AC, DC, TEMP, 

ALARM, AUX1÷AUX16 

Acoustic operation indication: 

Piezoelectric indicator ~75dB/0,3m 

The ALARM technical output of collective failure 

Relay type: 1A@ 30VDC/50VAC 

The 

F

MAINS

 

fuse in the 230V power supply circuit  

T 6,3A 

F1 ÷ F16

, glass fuses in the cameras AUX (+) 

power supply circuits

 

F 0,5A 

      

Mechanical parameters (tab. 3). 

Enclosure dimensions 

W=19”, H=2U; 482 x 88 x 223  mm (WxHxD) 

Fixation 

four-point butt mounting to RACK profiles 

– the set include 4 M6 cage nuts 

Net weight 

5,4kg / 5,9kg 

Enclosure 

Steel plate RAL 9005, black 

Connectors 

230V AC input: the IEC C14 socket with a fuse, power cable 1,5m  
(included) 
Outputs: BAT, ALARM, 

AUX1÷AUX16: Φ0,5-2,1 (AWG 24-12) 0,5-2mm

2

 

Notes 

Forced cooling (fan) 

       

Operation safety (tab.4). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Operating parameters (tab.5). 

Environmental class 

II 

Operating temperature 

-

10ºC...+45ºC 

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 
 
 
 
 
 
 

Содержание R1624T

Страница 1: ...R1624T v 1 0 R 24V 16x0 5A TOPIC RACK mounted power supply EN Edition 1 from 22 09 2017 Supercedes the edition...

Страница 2: ...r loss activation of the output fuse in the camera power supply circuit too high temperature of the PSU 70 C the PSU failure protections SCP short circuit protection OVP overvoltage protection overvol...

Страница 3: ...unting in standard RACK 19 cabinets 1 2 Block diagram Fig 1 The block diagram of the PSU 1 3 Description of PSU components and connectors Table 1 Components of the front panel of the power supply Elem...

Страница 4: ...www pulsar pl R1624T RACK POWER 4 Fig 2 The front power of the power supply unit Fig 3 The view of the PSU...

Страница 5: ...s tab 3 Enclosure dimensions W 19 H 2U 482 x 88 x 223 mm WxHxD Fixation four point butt mounting to RACK profiles the set include 4 M6 screws cage nuts Net weight 5 4kg 5 9kg Enclosure Steel plate RAL...

Страница 6: ...rmed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before...

Страница 7: ...re of the switch mode power supply GREEN LED on DC voltage in the AUX1 AUX16 output off no DC voltage in the AUX1 AUX16 output 3 2 Technical output The power supply is fitted with the ALARM output of...

Страница 8: ...ed with a fuse of the same type 4 2 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require perfor...

Отзывы: