PSBOC30012200   

 

 

 

 
 

3.2. Technical outputs

 

The PSU has indication outputs: 
 

 

EPS - absence of AC supply output

:  

-  OC  type  output  that  indicates  AC  power  loss.  Under  normal  status,  with  230V  AC  supply,  the  output  is 
connected  to  ground  (L  level 

–  0V).  In  case  of  power  loss,  the  PSU  will  switch  the  output  into  high 

impedance state hi-Z.  

relay output indicating the absence of AC supply. In case of power loss, the PSU module will switch the 

relay contacts.  

 

CAUTION!

 In Fig.5. the contact set in the potential-free status corresponds to a state with no AC 

power (AC power failure). 
 
 

 

PSU 

– technical output indicating absence of DC voltage at the PSU

-  OC  type  output  indicating  the  PSU  failure.  In  normal  state  (during  correct  operation)  the  output  is 
connected to ground (L level 

– 0V). In case of absence of DC voltage at the output (e.g. short circuit), the 

output is switched into high impedance state 

– hi-Z. 

     - relay output. In case of a failure, the contacts of the relay change over. 

 
 

CAUTION!

  In  the  Fig.5.  the  set  of  contacts  shows  a  potential-free  status  of  the  relay  which 

corresponds to a state with no DC power (PSU failure). 

 

 

LoB 

– technical output indicating battery voltage

:  

- OC type output. Under normal status (U

BAT

 > 11,5V) the output is connected to ground (L level 

– 0V). In 

case of decrease of battery voltage (U

BAT

 < 11,5V) the output is switched into high impedance state 

– hi-Z. 

      - relay output. In case of a battery voltage drop U

BAT

 < 11,5V, the contacts of the relay change over. 

The power supply unit does not feature a battery detection function. In the case of no battery or non battery 
connected, the output is in the normal mode. 

 
 

CAUTION!

 In the Fig.5. the set of contacts shows a potential-free status of the relay which 

corresponds to a state with low battery level (U

BAT

 <11,5V). 

 

 

 

Fig. 4. Electrical diagram of OC outputs. 

Fig. 5. Electrical diagram of relay outputs. 

 

 

4. Operation and use. 

4.1. Overload or short circuit of the PSU module output 

In case of an overload or a short circuit at the PSU output, the output voltage is automatically cut off. The 

voltage is restored automatically after removing the failure (overload). 

 
4.2. Disconnection of discharged battery.  

The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the  battery-assisted 

operation, reducing voltage below 9,5 V at the battery terminals will cause battery disconnection. 

 

 
4.3 Maintenance 

Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power  supply  network.  The  PSU  does  not  require  performing  any  specific  maintenance  measures.  However,  in 
case of significant dust ingress, it is recommended to clean the PSU with compressed air. 

 
 
 
 
 

Содержание PSBOC30012200

Страница 1: ...PSBOC30012200 v 1 0 PSBOC 13 8V 20A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 2 from 01 06 2016 Supercedes edition 1 from 09 04 2015...

Страница 2: ...ONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure...

Страница 3: ...relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC type 9 LoB output indicating battery low v...

Страница 4: ...table Short circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection melti...

Страница 5: ...y a qualified installer holding relevant permits and licenses applicable and required for a given country for 230V AC interference and low voltage installations The unit should be mounted in confined...

Страница 6: ...view of the PSU 3 Operating status indication 3 1 LED indication The PSU is equipped with 3 LEDs on the PCB board red LED Fig 2 element 1 normal status AC power permanently illuminated AC power absenc...

Страница 7: ...nected to ground L level 0V In case of decrease of battery voltage UBAT 11 5V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 11 5V the contac...

Страница 8: ...ays from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equi...

Отзывы: