background image

www.pulsar.pl 

 

 

 

 

PSBOC30012200   

 

 

 

 
 

Table 3. Mechanical specifications. 

Enclosure dimensions 

275x23 [mm] (LxWxH)  (+/- 2) 

Net/gross weight 

1,4kg / 1,5kg 

Connectors 

power supply: 

Φ0,63-2,50 (AWG 22-10) 

Outputs: 

Φ0,63-2,50 (AWG 22-10) 

technical outputs: 

Φ0,41-1,63 (AWG 26-14) 

battery outputs: 

Ф6/2,5mm

2

 

Led indication output: 3-pin 5 mm connector 

Notes 

Forced cooling - built-in fan. 

Table 4. Operation safety. 

Protection class PN-EN 60950-1:2007 

I (first) 

Degree of Protection PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between PSU input circuit and output circuits (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Table 5. Operating specifications. 

Operating temperature 

-

10ºC...+40ºC  

Environmental class 

II 

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 
 

2. Installation. 
 

2.1. Requirements 

The buffer PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable 

and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, without condensation) and temperature from -

10°C to +40°C. 

 
The device shall be mounted in a metallic enclosure (a cabinet, an intended case). In order to fulfil LVD and 

EMC requirements, the rules for: power-supply, encasing and screening shall be followed, according to application. 
The PSU provides voltage of 

U=13,8 V 

DC with current capacity: 

 

                       1. Output current 18A + 2A battery charging

*

 

                       2. Output current 16A + 4A battery charging

                       3. Output current 12A + 8A battery charging

*

 

  

                                                 Total device c battery: 20A max

*

 
2.2. Installation procedure. 

1. 

Before installation of the power supply unit, make sure that 230VAC power if cut off.

  

2. Mount the unit in the intended location.  
3. Connect the 230VAC power cables. Connect the PE cable (yellow-green) to an appropriate PSU terminal 
(marked with 

 - earth symbol).

 

 

 
The shock protection circuit shall be performed with a particular care, i.e. the yellow and green 
wire coat of the power cable shall stick to one side of the ‘PE’ terminal. Using the PSU without a 
properly made and fully operational shock protection circuit is UNACCEPTABLE! It can cause a 
device failure or an electric shock. 

 

 

                                                 

*

 

See chart 1

 

Содержание PSBOC30012200

Страница 1: ...PSBOC30012200 v 1 0 PSBOC 13 8V 20A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 2 from 01 06 2016 Supercedes edition 1 from 09 04 2015...

Страница 2: ...ONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure...

Страница 3: ...relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC type 9 LoB output indicating battery low v...

Страница 4: ...table Short circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection melti...

Страница 5: ...y a qualified installer holding relevant permits and licenses applicable and required for a given country for 230V AC interference and low voltage installations The unit should be mounted in confined...

Страница 6: ...view of the PSU 3 Operating status indication 3 1 LED indication The PSU is equipped with 3 LEDs on the PCB board red LED Fig 2 element 1 normal status AC power permanently illuminated AC power absenc...

Страница 7: ...nected to ground L level 0V In case of decrease of battery voltage UBAT 11 5V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 11 5V the contac...

Страница 8: ...ays from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equi...