4. Connect load/loads to proper output connectors of the power supply (positive pole is marked as +V, 
negative pole as -V) 
5. Connect the technical outputs to the central or other device. 
6. Connect the battery in accordance with the signs (colours). 

                    7. Check the PSU output voltage: 

- the PSU voltage without load should amount to U=13,8V DC. 
8. Once the tests and operation control have been completed, the enclosure/cabinet can be locked. 

 

 

Fig 3. Mechanical view of the PSU. 

 
 

3. Operating status indication. 

 

3.1. LED indication 

 

The PSU is equipped with 3 LEDs on the PCB board:

 

 - red LED (Fig.2, element 1) normal status (AC power): permanently illuminated. AC power absence is indicated by 
the AC diode going out.  
AC power absence is indicated by the AC diode going out.  

 

- green LED (Fig.2, element 2) indicates DC power at the PSU output. Under normal status the diode is permanently 
illuminated. In case of a short circuit or an overload, the diode is off. 
 
-  green  LED    (Fig.2,  element  3)  indicates  battery  voltage  level.  Under  normal  status  (U

BAT

  >  11,5V)  the  diode  is 

permanently illuminated. In case of decrease of battery voltage (U

BAT

 < 11,5V) the diode is off. 

 
 
 
 
 

 

 

Содержание PSBOC30012200

Страница 1: ...PSBOC30012200 v 1 0 PSBOC 13 8V 20A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 2 from 01 06 2016 Supercedes edition 1 from 09 04 2015...

Страница 2: ...ONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure...

Страница 3: ...relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC type 9 LoB output indicating battery low v...

Страница 4: ...table Short circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection melti...

Страница 5: ...y a qualified installer holding relevant permits and licenses applicable and required for a given country for 230V AC interference and low voltage installations The unit should be mounted in confined...

Страница 6: ...view of the PSU 3 Operating status indication 3 1 LED indication The PSU is equipped with 3 LEDs on the PCB board red LED Fig 2 element 1 normal status AC power permanently illuminated AC power absenc...

Страница 7: ...nected to ground L level 0V In case of decrease of battery voltage UBAT 11 5V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 11 5V the contac...

Страница 8: ...ays from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equi...

Отзывы: