www.pulsar.pl 

 

 

 

 

PSBOC251215 

 

 

 

 

 
 

 

3.1 LED indication 

 

The PSU is equipped with 3 LEDs on the PCB board: 

 - red LED (Fig.2, element 1) normal status (AC power): permanently illuminated. AC power absence is 
indicated by the AC diode going out.  
Caution! LED indicates power absence if the outage lasts >10s. 

 

-  green  LED  (Fig.2,  element  2)  indicates  DC  power  at  the  PSU  output.  Under  normal  status  the  diode  is 
permanently illuminated. In case of a short circuit or an overload, the diode is off. 
 
- green LED  (Fig.2, element 3) indicates battery voltage level. Under normal status (U

BAT

 > 11,5V) the diode is 

permanently illuminated. In case of decrease of battery voltage (U

BAT

 < 11,5V) the diode is off. 

 

3.2 Technical outputs

 

The PSU has indication outputs: 
 

 

FAC - absence of AC supply output: - OC type output that indicates AC power loss. Under normal status, 
with 230V AC supply, the output is connected to ground (L level – 0V). In case of power loss, the PSU will 
switch the output into high impedance state hi-Z after approx. 10s. 
 

 

FAC - absence of AC supply output: - relay output indicating the absence of AC supply. In case of power 
loss, the PSU module will switch the relay contacts after approx. 10 seconds. 
 

 
CAUTION! In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 
power (AC power failure). 
 
 

 

 

FPS  –  technical  output  indicating  absence  of  DC  voltage  at  the  PSU:  OC  type  output  indicating  the 
PSU failure. In normal state (during correct operation) the output is connected to ground (L level – 0V). In 
case of absence of DC voltage at the output (e.g. short circuit), the output is switched into high impedance 
state – hi-Z. 

 

 

FLB – technical output indicating battery voltage: OC type output. Under normal status (U

BAT

 > 11,5V) 

the output is connected to ground (L level – 0V). In case of decrease of battery voltage (U

BAT

 < 11,5V) the 

output is switched into high impedance state – hi-Z. 
 

 

Fig. 4. Electrical diagram of OC outputs. 

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU module output 
In case of an overload or a short circuit at the PSU output, the output voltage is automatically cut off. The 

voltage is restored automatically after removing the failure (overload). 

 
4.2 Battery-assisted operation.  
In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

 
 

 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the 

battery-assisted operation,  reducing voltage  below  9,5V  at  the battery  terminals  will  cause 
battery disconnection. 

 
 
 
 

Содержание PSBOC251215

Страница 1: ...PSBOC251215 v 1 0 PSBOC 13 8V 1 5A OC Caged switched mode buffer power supply unit EN Edition 2nd 19th July 2012 Supersedes edition 1st 10th Mar 2012...

Страница 2: ...al description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED in...

Страница 3: ...sence of DC power 3 LED indicating correct battery voltage 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type...

Страница 4: ...SU systems 40 mA Battery charging current 0 5A Short circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection...

Страница 5: ...ng temperature 10 C 40 C Storage temperature 20 C 60 C Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolati...

Страница 6: ...of the power cable shall stick to one side of the PE terminal Using the PSU without a properly made and fully operational shock protection circuit is UNACCEPTABLE It can cause a device failure or an...

Страница 7: ...ts after approx 10 seconds CAUTION In Fig 2 the contact set in the potential free status corresponds to a state with no AC power AC power failure FPS technical output indicating absence of DC voltage...

Страница 8: ...ct 6 Should the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenience however not later that within 14 days from the delivery to the service centre of t...

Отзывы: