Temperature characteristics. 

 

 

 
 
 
 
 

Chart 1.  
Acceptable output current from the PSU 
depending on ambient temperature. 

 

 

Mechanical specifications (tab. 3). 

Enclosure dimensions 

110 x 78 x 36 +23 [mm] (LxWxH) [mm] (+/- 2) 

Net/gross weight 

0,28kg / 0,31kg 

Connectors 

power supply, technical outputs: 

Φ

0,63÷2,5   I/O PCB : 

Φ

0,41÷1,63   

BAT battery outputs: 6,3F-2,5/40cm, 
Led indication output: 3-pin 5 mm connector 

Operation safety (tab.4). 

Protection class PN-EN 60950-1:2007 

I (first) 

Degree of Protection PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between PSU input circuit and output circuits (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
500  V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC  

 

Operating specifications (tab.5). 

Operating temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 
 
 

2. Installation. 
 

2.1 Requirements 
 
The buffer PSU is to be mounted  by a qualified installer, holding relevant permits and licenses (applicable 

and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, without condensation) and temperature from -10°C to +40°C. 

 
The  device  shall  be  mounted  in  a  metallic  enclosure  (a cabinet,  an  intended  case).  In  order  to fulfil  LVD 

and  EMC  requirements,  the  rules  for:  power-supply,  encasing  and  screening  shall  be  followed,  according  to 
application.  
  

 
During  normal  operation,  the  total  current  drawn  by  the  device  may  not  exceed  I=1A. 
Maximum battery charging current: 0,5A. Total current of the rec battery: 1,5A max. 

 
 

 

Содержание PSBOC251215

Страница 1: ...PSBOC251215 v 1 0 PSBOC 13 8V 1 5A OC Caged switched mode buffer power supply unit EN Edition 2nd 19th July 2012 Supersedes edition 1st 10th Mar 2012...

Страница 2: ...al description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED in...

Страница 3: ...sence of DC power 3 LED indicating correct battery voltage 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type...

Страница 4: ...SU systems 40 mA Battery charging current 0 5A Short circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection...

Страница 5: ...ng temperature 10 C 40 C Storage temperature 20 C 60 C Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolati...