PULSAR MEASUREMENT
57
6.
Click Erase-Program-Verify, and then wait for the process to
complete.
7.
When “Verification successful” message is displayed, click Run
Application then click Disconnect.
8.
Close the Bootloader Interface program and reconnect to the device
using FlowPulse PC.
When the device is in Bootloader mode, the Red led flashes continuously
and the Green led is off.
In step (4), if the Bootloader Interface software does not connect to the
device within 40 seconds, the device will resume normal operation with its
current firmware. Repeat step (2) to put the device into Bootloader mode
again.
High Noise Environment
Flow Pulse may be affected by both ultrasonic and electrical noise. Exercise
the following precautions during installation:
1.
Avoid using other clamp-on ultrasonic device less than 1 metre from
Flow Pulse.
2.
Ensure that screened cables are used and that the Flow Pulse
enclosure is properly Earthed
–
do not connect the cable screen to
the Ground (-) terminal of the power supply or the mA output. If
RS485 is not used, the cable screen should be connected to the
enclosure using the cable entry gland. If RS485 is used, connect
cable screen to the RS485 screen terminal, then earth the FlowPulse
enclosure separately if possible.
3.
Relocate the device away from pumps, valves, tees, or elbows where
possible.