PULSAR MEASUREMENT
33
Relay/Alarm
The Relay/Alarm parameters allow the set points and switching mode to be
configured. Figure 6 shows the alarm zones defined by the low and high set
points, and the function of the different alarm modes.
ALARM
MODE
ZONE LOW
ZONE MID
ZONE HIGH
Low (
Default
)
Alarm ON
No Change
Alarm OFF
High
Alarm OFF
No Change
Alarm ON
Out of Range
Alarm ON
Alarm OFF
Alarm ON
Alarm OFF
De-energise
Alarm ON
Alarm OFF
Figure 6: The alarm modes and its effect in the relay/alarm zones as defined
by the low and high set points.
Flow Rate
Time
High
Setpoint
Low
Setpoint
Zone
Low
Zone
Mid
Zone
High