background image

www.pulsar.pl   

 

 

 

EN54-7A40LCD 

 

 

 

    

RED POWER

 

 
 

21 

      Table 10. List of PSU message codes.  

Message 

code 

Description 

I00 

Power supply start-up 

I01 

AC power back 

I02 

AUX fuse replaced 
AUX2 fuse replaced 

I03 

BAT fuse replaced  

I04 

Battery connected 

I05 

Battery OK 

I06 

Battery temperature OK 

I07 

AC voltage OK 

I08 

EXTo output ON 

I09 

EXTo output OFF 

I10 

Battery test 

– START 

I11 

PSU cover closed 

I12 

Imax_a over limit 

I13 

Iaux decr. below Imax_a 

 

 

6.5. Technical outputs. 

The PSU is equipped with galvanically isolated indication outputs changing status after a specified event: 
 

 

EPS FLT 

– output indicating 230 V power loss

The  output  indicates  230  V  power  loss.  Under  normal  status,  with  the  230  V  power  on,  the  output  is 

closed.  In  case  of  power  failure,  the  PSU  will  switch  the  output  into  the  open  position  after  a  time  lag 
determined in the „ Delay time for EPS output” menu (see section 7.2.4). 

 

 

APS FLT 

– output indicating battery failure.

  

The output indicates a failure in the battery circuit. Under normal status (during correct operation) the  

output is closed. In case of failure, the PSU will switch the output into the open position. Failure can be triggered by 
the following events: 
 

 

- faulty batteries 

 

 

- undercharged batteries 

 

 

- disconnected batteries 

 

 

- high resistance of the battery circuit 

 

 

- battery voltage below 23 V during battery-assisted operation 
- blown battery fuse  
- no continuity in the battery circuit 

 

 

PSU FLT 

– output indicating PSU failure

.  

The  output  indicates  the  PSU  failure.  Under  normal  status  (during  correct  operation)  the  output  is 

closed. In case of PSU failure, it will switch into the open position. Failure can be triggered by the  
following events: 

 

 

- U

AUX1, AUX2

 output voltage below 26 V 

 

 

- U

AUX1, AUX2

 output voltage over 29,2 V 

 

 

- battery charging circuit failure 

 

 

- blown F

AUX1

 or F

AUX2 

fuse  

 

 

- exceeding the rated current of the PSU 
- activation of overvoltage protection OVP 
 - mains supply voltage over 254 V AC 
- mains supply voltage  below 195 V AC 
- to high battery temperature (>65 

°C) 

- temperature sensor failure, t < -20 

°C or t > 80 °C 

- enclosure opening 

– TAMPER 

- internal damage of the PSU 

 

 

- LCD panel damage 
 
 
 
 
 
 
 
 

Содержание EN54-7A40LCD

Страница 1: ...EN54 7A40LCD v 1 1 EN54 27 6V 7A 2x40Ah LCD power supply for fire alarm systems EN Edition 5 from 31 01 2019 Supersedes the edition 4 from 11 01 2016 LCD Version...

Страница 2: ...LOSURE OPENING TAMPER 23 6 8 INCREASING THE NUMBER OF OUTPUTS WITH OPTIONAL EN54 LB4 OR EN54 LB8 FUSE MODULES 23 6 9 OVERVOLTAGE PROTECTION OF THE PSU OUTPUT OVP 24 6 10 PSU OVERLOAD 24 6 11 INDICATIO...

Страница 3: ...39 8 8 STANDBY TIME 39 9 REMOTE MONITORING OPTIONS WI FI ETHERNET RS485 USB 40 9 1 COMMUNICATION VIA THE USB TTL INTERFACE 40 9 2 ETHERNET NETWORK COMMUNICATION 40 9 3 THE WI FI WIRELESS COMMUNICATION...

Страница 4: ...cation for remote monitoring of power supplies for PC and Android Phones remote control options WiFi Ethernet RS485 USB remote battery test required additional modules cooperation with optional EN54 L...

Страница 5: ...nual Red mounting spacers 4 pieces Red metal mounting brackets for hanging the power supply 4 pieces M8x16 mounting screws 4 pieces PG9 cable glands 4 pieces PG11 cable glands 4 pieces Battery serial...

Страница 6: ...circuit YES YES Low battery indication YES YES Deep discharge battery protection YES YES Protection against short circuit of the battery terminals YES YES Blown battery fuse indication YES YES Chargi...

Страница 7: ...put current Imax b 7 A In case of power loss the PSU switches to battery power providing uninterruptible power supply The PSU is enclosed in a metal casing color RAL 3001 red with battery housing for...

Страница 8: ...tage OVL PSU overload APS battery failure PSU PSU failure ALARM collective failure EXTi EXTi input status EXTo EXTo relay output status LB battery charging 11 Terminals AC AC power input EPS FLT techn...

Страница 9: ...Components of the PCB of the EMC filter Fig 3 Element No Description FMAINS fuse in the power supply circuit 230 V T6 3 A 250 V L N power supply connector 230 V protective connector Connector for conn...

Страница 10: ...al module INTR INTE INTW 5 Place to install the EN54 LB4 or EN54 LB8 fuse module 6 TAMPER microswitch contacts of antisabotage protection NC 7 EMC filter module see Table 2 Fig 3 8 2x40 Ah batteries 9...

Страница 11: ...attention should be paid to the proper installation of the cables Installation cables should be firmly connected to the battery side terminals and to the power supply connector The side walls of the h...

Страница 12: ...failure EXTi input of collective failure 5 Install the batteries in a designated area of the enclosure see Fig 4 Connect the batteries with the PSU paying special attention to the correct polarity Bat...

Страница 13: ...ters which should be displayed Fig 7 Control panel Table 6 The description of the buttons and LEDs of the LCD panel moves the pointer on the screen next screen selection selection approval quit editin...

Страница 14: ...he LCD Main screen of the LCD displays the basic electrical parameters and indicates the current status of the power supply Fig 9 Main screen of the LCD The resolution of voltage and current measureme...

Страница 15: ...starts the preview menu allowing to choose one of the four available PSU screens Use the or buttons to choose a proper screen and press the SET button to confirm current parameters of the PSU see sec...

Страница 16: ...n 6 10 6 11 PSU failure indication highlighted PSU failure See sections 6 4 6 6 5 Battery failure indication highlighted battery failure See sections 6 4 6 6 5 EXTi input status indication highlighted...

Страница 17: ...re of the highest priority If there are more than five failures at the same time use the or buttons to display the next failure 6 4 4 LCD screen history of the parameters To set the screen press the E...

Страница 18: ...inimum the lowest value measured during 5 minutes maximum the highest value measured during 5 minutes of the following parameters UAC mains supply voltage 230 V UAC MIN mains supply voltage minimum UA...

Страница 19: ...ying information about the fault type time of occurrence and the values of other electrical parameters In addition the diagnostic system assigns the failure code for a particular event on the basis of...

Страница 20: ...w 26 V Battery charging circuit failure F09 Low AUX1 voltage PSU FLT ALARM Output voltage below 26 V Low AUX2 voltage F10 Low battery voltage APS FLT ALARM The battery voltage has dropped below 23 V d...

Страница 21: ...a failure in the battery circuit Under normal status during correct operation the output is closed In case of failure the PSU will switch the output into the open position Failure can be triggered by...

Страница 22: ...t will trigger PSU failure storing the information about the event in the internal memory and sending the signal about the failure to the ALARM output The EXT IN technical input has been made with gal...

Страница 23: ...creasing the number of outputs with optional EN54 LB4 or EN54 LB8 fuse modules The PSU has two independently protected outputs for connecting the AUX1 and AUX2 receivers If the power supply unit is co...

Страница 24: ...system is indicated by the OVP yellow LED on the PCB board and the PSU FLT and ALARM outputs 6 10 PSU overload The PSU is fitted with the LED OVL overload on the PCB informing about output overload If...

Страница 25: ...password full access to the PSU s settings User s password locked access to the PSU settings menu Table11 Access ranges PASSWORD Access range Control panel settings PSU settings SERVICE USER Preset p...

Страница 26: ...hange it To do this choose a password that will be changed user s password or service password and enter the new one 7 1 3 Disabling the password If the password is not required it can be turned off T...

Страница 27: ...by pressing the SET button When on the keyboard will be locked automatically if no buttons are pressed within 5 minutes After this time pressing any button on the control panel will display a window w...

Страница 28: ...6 NO acoustic indication OFF Section 7 2 2 EXTo output ON output ON see section 4 9 OFF output OFF Section 7 2 3 Delay time for EPS output Setting the delay time for 230 V power failure indication 10s...

Страница 29: ...1 1 signal every 10s battery mode AC power failure 2 1 signal every 10s mains operation Battery failure undercharged batteries 3 2 signals every 10s battery mode Low battery level 4 Fast signals batt...

Страница 30: ...vel control Z2 jumper must be on Information about the changes in the EXTo output is written in the event log of the PSU use the or buttons to display the EXTo output menu press the SET button the pro...

Страница 31: ...ers responsible for communication between the PSU and the computer namely the address parity and speed should have the same settings for both the PSU and the PowerSecurity program Communication addres...

Страница 32: ...e the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 if these values were changed they should be restored to original settin...

Страница 33: ...he displayed messages Intensity of the LCD backlight can be set in the range from 0 to100 in 10 intervals The display features a function of constant or temporary backlight mode In temporary mode the...

Страница 34: ...the front panel of the power supply 7 3 2 Setting the date The Date menu in the Control panel menu enables setting the correct date according to which error messages and operation history will be save...

Страница 35: ...s the SET button the prompt will appear next to the hour digits use the or buttons to set the hour press the SET button the prompt will appear next to the minute position use the or buttons to set the...

Страница 36: ...st of the display text use the or buttons to display the Contrast menu press the SET button the prompt will appear at the end of the line use the or buttons to set the contrast confirm by pressing the...

Страница 37: ...RED POWER 37 press the SET button the prompt will appear at the end of the line use the or buttons to select YES blinking light indicating failure ON NO blinking light indicating failure OFF confirm...

Страница 38: ...e of incorrect connection the FBAT fuse in the battery circuit becomes damaged The return to normal operation is possible only after replacing the fuse and correct connection of the batteries 8 4 Deep...

Страница 39: ...hence temperature readings should not be confused with the ambient temperature Temperature measurement and compensation of the battery charging voltage can extend the life of the batteries 8 8 Standby...

Страница 40: ...power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 8 8 9 1 Communication via the USB TTL interface The easiest way of...

Страница 41: ...mounted in a hermetic enclosure protecting against adverse environmental conditions Fig 31 Ethernet communication using the RS485 Ethernet INTRE interface 9 3 The Wi Fi wireless communication The Wi...

Страница 42: ...t adverse environmental conditions Fig 33 The The Wi Fi communication using the RS485 WIFI INTRW interface 9 4 RS485 network communication Another type of network communication is the RS485 communicat...

Страница 43: ...wer supplies in case of failures the backlight changes accordingly in both the manager window and the Windows taskbar In addition the program allows you to download the operation history of the power...

Страница 44: ...ynoptic board or the list mode This is especially useful when the PowerSecurity program works with a large number of power supplies The application enables both visualization and analysis of read data...

Страница 45: ...tage AUX disconnection automatic return Short circuit protection SCP F8 A FAUX1 FAUX2 melting fuse failure requires fuse replacement Overload protection OLP Hardware Software Battery circuit protectio...

Страница 46: ...INTW interface WiFi wireless communication RS485 Ethernet INTRE interface RS485 Ethernet communication RS485 WiFi INTRW interface RS485 WiFi wireless communication Table 16 Mechanical parameters Encl...

Страница 47: ...ters Environmental class EN 12101 10 2007 2 Operating temperature 5 C 75 C Storing temperature 25 C 60 C Relative humidity 20 90 no condensation Sinusoidal vibrations during operation 10 50 Hz 50 150...

Страница 48: ...032 is about six years After this period the battery will need to be replaced Battery replacement of the LCD panel should be done during mains operation or battery assisted operation in order to avoid...

Отзывы: