8. Reserve power supply circuit. 

 

The  PSU  is  fitted  with  intelligent  circuits:  battery  charging  circuit  with  the  function  of  the  accelerated 

charging and battery control, which main task is to monitor the condition of the batteries and the connections in the 
circuit. 
If the controller detects a power failure  in the battery  circuit, appropriate indication and activation  of the APS FLT 
and ALARM technical outputs takes place. 

 

       8.1. Battery detection. 

The  control  unit  of  the  PSU  checks  the  voltage  at  the  battery  terminal  and,  depending  on  the  measured 

values, determines the appropriate reaction: 

U

BAT

 below 4 V     - batteries not connected to the PSU circuits  

U

BAT

 = 4 to 20 V  - faulty batteries 

U

BAT

 over 20 V    - batteries connected to the PSU circuits 

 

       8.2. Protection against short -circuit of the battery terminals. 

 

The  PSU  is  fitted  with  the  circuit  protecting  against  short-circuit  of  the  battery  terminals.  In  case  of  short 

circuit, control circuit immediately disconnects the batteries from the rest of the power supply circuit, so the loss of 
output  voltage  on  power  supply  outputs  is  not  observed.  Automatic  reconnection  of  the  batteries  to  the  PSU's 
circuits is only possible after the removal of the short-circuit and correct connection of the circuits. 
 

       8.3. Protection against reverse battery connection. 

The PSU is protected against reverse connection of the battery terminals. In case of incorrect connection, 

the  F

BAT

  fuse  in  the  battery  circuit  becomes  damaged.  The  return  to  normal  operation  is  possible  only  after 

replacing the fuse and correct connection of the batteries. 

 

     8.4. Deep discharge battery protection UVP. 

The  PSU  is  fitted  with  the  disconnection  system  and  the  battery  discharge  indication.  If  the  voltage  at  the 

battery  terminals  drops  below  20  V

±0.2  V  during  battery-assisted  operation,  acoustic  indication  will  be  activated 

and the batteries will be disconnected within 15s.  

The  batteries  are  reconnected  to  the  power  supply  unit  automatically  once  the  ~230  V  mains  supply  is 

restored. 
 

      8.5. Battery test. 

The  PSU  runs  dynamic  battery  test  every  5  minutes,  temporarily  switching  the  receivers  to  the  battery 

operation  mode.  During  testing,  the  control  unit  of  the  PSU  measures  the  electrical  parameters  according  to  the 
implemented measuring method.  
A negative result occurs when: 
- the battery circuit continuity is interrupted,  

resistance in the battery circuit increases above 300 mΩ  

- the battery terminal voltage drops below 24 V. 

The battery test can be activated manually from the main menu (see section 7.2.1), for example to test the 

replaced batteries. 

The  PSU  is  protected  against  too  frequent  performing  of  the  battery  test,  which  could  result  in 

undercharging. The protection involves blocking the ability to perform test for 60 seconds from the last activation.  



n this case, the LCD will display the "

WAIT” message in the PSU Settings -> PSU -> Battery test menu. 

 

 

Fig. 27. Temporary lock of the battery test. 

 

This function can be disabled by putting the Z2 jumper on the power supply board (Fig.2 [8]). 
 
 
 
 
 

Содержание EN54-7A40LCD

Страница 1: ...EN54 7A40LCD v 1 1 EN54 27 6V 7A 2x40Ah LCD power supply for fire alarm systems EN Edition 5 from 31 01 2019 Supersedes the edition 4 from 11 01 2016 LCD Version...

Страница 2: ...LOSURE OPENING TAMPER 23 6 8 INCREASING THE NUMBER OF OUTPUTS WITH OPTIONAL EN54 LB4 OR EN54 LB8 FUSE MODULES 23 6 9 OVERVOLTAGE PROTECTION OF THE PSU OUTPUT OVP 24 6 10 PSU OVERLOAD 24 6 11 INDICATIO...

Страница 3: ...39 8 8 STANDBY TIME 39 9 REMOTE MONITORING OPTIONS WI FI ETHERNET RS485 USB 40 9 1 COMMUNICATION VIA THE USB TTL INTERFACE 40 9 2 ETHERNET NETWORK COMMUNICATION 40 9 3 THE WI FI WIRELESS COMMUNICATION...

Страница 4: ...cation for remote monitoring of power supplies for PC and Android Phones remote control options WiFi Ethernet RS485 USB remote battery test required additional modules cooperation with optional EN54 L...

Страница 5: ...nual Red mounting spacers 4 pieces Red metal mounting brackets for hanging the power supply 4 pieces M8x16 mounting screws 4 pieces PG9 cable glands 4 pieces PG11 cable glands 4 pieces Battery serial...

Страница 6: ...circuit YES YES Low battery indication YES YES Deep discharge battery protection YES YES Protection against short circuit of the battery terminals YES YES Blown battery fuse indication YES YES Chargi...

Страница 7: ...put current Imax b 7 A In case of power loss the PSU switches to battery power providing uninterruptible power supply The PSU is enclosed in a metal casing color RAL 3001 red with battery housing for...

Страница 8: ...tage OVL PSU overload APS battery failure PSU PSU failure ALARM collective failure EXTi EXTi input status EXTo EXTo relay output status LB battery charging 11 Terminals AC AC power input EPS FLT techn...

Страница 9: ...Components of the PCB of the EMC filter Fig 3 Element No Description FMAINS fuse in the power supply circuit 230 V T6 3 A 250 V L N power supply connector 230 V protective connector Connector for conn...

Страница 10: ...al module INTR INTE INTW 5 Place to install the EN54 LB4 or EN54 LB8 fuse module 6 TAMPER microswitch contacts of antisabotage protection NC 7 EMC filter module see Table 2 Fig 3 8 2x40 Ah batteries 9...

Страница 11: ...attention should be paid to the proper installation of the cables Installation cables should be firmly connected to the battery side terminals and to the power supply connector The side walls of the h...

Страница 12: ...failure EXTi input of collective failure 5 Install the batteries in a designated area of the enclosure see Fig 4 Connect the batteries with the PSU paying special attention to the correct polarity Bat...

Страница 13: ...ters which should be displayed Fig 7 Control panel Table 6 The description of the buttons and LEDs of the LCD panel moves the pointer on the screen next screen selection selection approval quit editin...

Страница 14: ...he LCD Main screen of the LCD displays the basic electrical parameters and indicates the current status of the power supply Fig 9 Main screen of the LCD The resolution of voltage and current measureme...

Страница 15: ...starts the preview menu allowing to choose one of the four available PSU screens Use the or buttons to choose a proper screen and press the SET button to confirm current parameters of the PSU see sec...

Страница 16: ...n 6 10 6 11 PSU failure indication highlighted PSU failure See sections 6 4 6 6 5 Battery failure indication highlighted battery failure See sections 6 4 6 6 5 EXTi input status indication highlighted...

Страница 17: ...re of the highest priority If there are more than five failures at the same time use the or buttons to display the next failure 6 4 4 LCD screen history of the parameters To set the screen press the E...

Страница 18: ...inimum the lowest value measured during 5 minutes maximum the highest value measured during 5 minutes of the following parameters UAC mains supply voltage 230 V UAC MIN mains supply voltage minimum UA...

Страница 19: ...ying information about the fault type time of occurrence and the values of other electrical parameters In addition the diagnostic system assigns the failure code for a particular event on the basis of...

Страница 20: ...w 26 V Battery charging circuit failure F09 Low AUX1 voltage PSU FLT ALARM Output voltage below 26 V Low AUX2 voltage F10 Low battery voltage APS FLT ALARM The battery voltage has dropped below 23 V d...

Страница 21: ...a failure in the battery circuit Under normal status during correct operation the output is closed In case of failure the PSU will switch the output into the open position Failure can be triggered by...

Страница 22: ...t will trigger PSU failure storing the information about the event in the internal memory and sending the signal about the failure to the ALARM output The EXT IN technical input has been made with gal...

Страница 23: ...creasing the number of outputs with optional EN54 LB4 or EN54 LB8 fuse modules The PSU has two independently protected outputs for connecting the AUX1 and AUX2 receivers If the power supply unit is co...

Страница 24: ...system is indicated by the OVP yellow LED on the PCB board and the PSU FLT and ALARM outputs 6 10 PSU overload The PSU is fitted with the LED OVL overload on the PCB informing about output overload If...

Страница 25: ...password full access to the PSU s settings User s password locked access to the PSU settings menu Table11 Access ranges PASSWORD Access range Control panel settings PSU settings SERVICE USER Preset p...

Страница 26: ...hange it To do this choose a password that will be changed user s password or service password and enter the new one 7 1 3 Disabling the password If the password is not required it can be turned off T...

Страница 27: ...by pressing the SET button When on the keyboard will be locked automatically if no buttons are pressed within 5 minutes After this time pressing any button on the control panel will display a window w...

Страница 28: ...6 NO acoustic indication OFF Section 7 2 2 EXTo output ON output ON see section 4 9 OFF output OFF Section 7 2 3 Delay time for EPS output Setting the delay time for 230 V power failure indication 10s...

Страница 29: ...1 1 signal every 10s battery mode AC power failure 2 1 signal every 10s mains operation Battery failure undercharged batteries 3 2 signals every 10s battery mode Low battery level 4 Fast signals batt...

Страница 30: ...vel control Z2 jumper must be on Information about the changes in the EXTo output is written in the event log of the PSU use the or buttons to display the EXTo output menu press the SET button the pro...

Страница 31: ...ers responsible for communication between the PSU and the computer namely the address parity and speed should have the same settings for both the PSU and the PowerSecurity program Communication addres...

Страница 32: ...e the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 if these values were changed they should be restored to original settin...

Страница 33: ...he displayed messages Intensity of the LCD backlight can be set in the range from 0 to100 in 10 intervals The display features a function of constant or temporary backlight mode In temporary mode the...

Страница 34: ...the front panel of the power supply 7 3 2 Setting the date The Date menu in the Control panel menu enables setting the correct date according to which error messages and operation history will be save...

Страница 35: ...s the SET button the prompt will appear next to the hour digits use the or buttons to set the hour press the SET button the prompt will appear next to the minute position use the or buttons to set the...

Страница 36: ...st of the display text use the or buttons to display the Contrast menu press the SET button the prompt will appear at the end of the line use the or buttons to set the contrast confirm by pressing the...

Страница 37: ...RED POWER 37 press the SET button the prompt will appear at the end of the line use the or buttons to select YES blinking light indicating failure ON NO blinking light indicating failure OFF confirm...

Страница 38: ...e of incorrect connection the FBAT fuse in the battery circuit becomes damaged The return to normal operation is possible only after replacing the fuse and correct connection of the batteries 8 4 Deep...

Страница 39: ...hence temperature readings should not be confused with the ambient temperature Temperature measurement and compensation of the battery charging voltage can extend the life of the batteries 8 8 Standby...

Страница 40: ...power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 8 8 9 1 Communication via the USB TTL interface The easiest way of...

Страница 41: ...mounted in a hermetic enclosure protecting against adverse environmental conditions Fig 31 Ethernet communication using the RS485 Ethernet INTRE interface 9 3 The Wi Fi wireless communication The Wi...

Страница 42: ...t adverse environmental conditions Fig 33 The The Wi Fi communication using the RS485 WIFI INTRW interface 9 4 RS485 network communication Another type of network communication is the RS485 communicat...

Страница 43: ...wer supplies in case of failures the backlight changes accordingly in both the manager window and the Windows taskbar In addition the program allows you to download the operation history of the power...

Страница 44: ...ynoptic board or the list mode This is especially useful when the PowerSecurity program works with a large number of power supplies The application enables both visualization and analysis of read data...

Страница 45: ...tage AUX disconnection automatic return Short circuit protection SCP F8 A FAUX1 FAUX2 melting fuse failure requires fuse replacement Overload protection OLP Hardware Software Battery circuit protectio...

Страница 46: ...INTW interface WiFi wireless communication RS485 Ethernet INTRE interface RS485 Ethernet communication RS485 WiFi INTRW interface RS485 WiFi wireless communication Table 16 Mechanical parameters Encl...

Страница 47: ...ters Environmental class EN 12101 10 2007 2 Operating temperature 5 C 75 C Storing temperature 25 C 60 C Relative humidity 20 90 no condensation Sinusoidal vibrations during operation 10 50 Hz 50 150...

Страница 48: ...032 is about six years After this period the battery will need to be replaced Battery replacement of the LCD panel should be done during mains operation or battery assisted operation in order to avoid...