5.5.1. Performing the battery test
– „tSt”
The "tSt" function runs a manual test of the batteries connected to the power supply. If the test result is
negative, it will be signaled by the power supply with an appropriate message, a beeping sound, while the APS and
ALARM technical outputs will change their status into opposite.
-
Simultaneously press the „<,>” rightmost and leftmost buttons and hold for
at least 5 seconds
-
The „tSt” parameter will be displayed
-
Press „OK”
-
The „On” parameter will be displayed
-
Press „OK”
- The information about starting the battery test will be displayed
-
After the battery test, the „tSt” parameter will be displayed
(In the event of a negative test result, the power supply will indicate a failure)
-
To return to the main menu, simultaneously press the „<,>” rightmost
and leftmost buttons
5.5.2. Calibration of the battery circuit” "CAL"
The battery circuit calibration function measures the reference resistance in the battery circuits
independently for each battery string. Calibration should be performed after the installation of new batteries.
-
Simultaneously press the „<,>” rightmost and leftmost buttons and hold
for at least 5 seconds
-
The „tSt” parameter will be displayed
-
Use the „<” or „>” buttons in order to display the "CAL" parameter
-
Press the „OK” button and hold it down for at least 5 seconds
- The information about the readiness for the calibration process will be displayed