www.pulsar.pl
DSOP24V
10
Table 4. Technical parameters of safety strips.
Model
LZ1F1B
LZ1F2B
LZ3F1B
LZ3F2B
Connection to the mains
Single-phase 230V
3-phase 3x230V/400V
The main overcurrent circuit breaker.
1 + N-pole
C16 or C20
The rated short-circuit breaking
capacity 6kA
3 + N-pole
C16 or C20
The rated short-circuit breaking
capacity 6kA
Surge protection
L, N
type 3 (D) according to the EN
61643-11 standard
L1, L2, L3, N
type 3 (D) according to the EN
61643-11 standard
The overcurrent circuit breaker of the
power supply unit
1 - pole, C6
Battery circuit protection
63A or 100A
22x58mm
442000 (aM)
2x63A or
2x100A
22x58mm
442000 (aM)
63A or 100A
22x58mm
442000 (aM)
2x63A or
2x100A
22x58mm
442000 (aM)
Recommended cable parameters
OMY 3 x 1.5 mm
2
…4 mm
2,
YLY 3 x 1.5 mm
2
…4 mm
2
OMY 5 x 2.5 mm
2
…4 mm
2
YLY 5 x 1.5 mm
2
…4 mm
2
Dimensions
Standard RACK 19”
H= 3U
4.2. 230VAC LDxxxx voltage distribution terminal.
The voltage distribution terminal is equipped with 230V connection sockets and is used to supply
components of the DSO. Depending on the number of devices and the amount of power consumption, the terminal
can have a 1-phase or 3-phase connection. The 3-phase version enables a more uniform load per phase of the
power grid. The terminal is placed in the rear of the cabinet.
Fig. 9. A LD1F6G voltage distribution terminal.
Fig. 10. The LD3F9G voltage distribution terminal.
Table 5. Technical parameters of distribution terminals.
Model
LD1F6G
LD3F9G
The number of outlets
6
9
Protection
C16 or C20
3xC16 or 3xC20
Dimensions
Standard RACK 19”
H= 1U