Pulsar Blue Power PSBS 2012B Скачать руководство пользователя страница 8

www.pulsar.pl                                                       

PSBS2012B                                                                  

BLUE POWER

     

 

AC OK: 

 

on – The PSU supplied with 230V AC voltage 

 

 

off – no 230V AC mains supply  

DC OK: 

 

on – DC voltage at the AUX output  

 

off - no DC voltage at the AUX output 

BAT OK: 

 

on – battery voltage  U

BAT

 > 11,5V 

 

off – battery voltage  U

BAT

 < 11,5V 

 

The  power  supply  is  designed  for  a  continuous  operation  and   is  not  equipped  with  a  power-switch. 

Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the user should 
be informed how to disconnect the power supply unit from the mains supply (usually by assigning an appropriate fuse in 
the fuse box). The electrical system shall be made in accordance with applicable standards and regulations. 

 
2.2 Installation procedure. 

 

1.  Before installation, make sure that the voltage in the 230V power-supply circuit is cut off. 

2.  Mount the PSU in a selected location and connect the wires. 
3.  Connect the power cables (230V AC) to the L-N terminals of the PSU. Connect the ground wire to the terminal 

marked with the PE symbol (power supply module connector). Use a three-core cable (with a yellow and green 
PE protection wire) to make the connection. The power cables should be connected to the appropriate terminals 
on the connection board through the bushing. 

 

The shock protection circuit shall be done with a particular care: the yellow and green wire 
coat  of    the    power    cable    should  be  connected  to    the    terminal    marked    with    the  PE  

symbol.  Operation  of  the  PSU  without  the  properly  made  and  fully  operational  shock 
protection circuit is UNACCEPTABLE! It can cause damage to the equipment or an electric 

shock

  

 

4.  Connect the receiver cables to the AUX terminals at the power supply board. 
5.  If needed, connect the device cables to the technical outputs: 

- EPS; technical output indicating AC power failure 
- PSU; technical output indicating PSU failure. 

- LoB; technical output indicating low battery voltage 
- Optional installation of the MPSBS relay module changing technical outputs of the OC type to relay type (page 

9, section. 3.3) 
6.  Use the I

BAT

 jumper to set the maximum battery charging current, taking into account the battery parameters. 

7.  Use  the  P

BAT

  jumper  to  set  to  turn  on/off  deep  discharge  battery  protection  U<10V  (+/-5%). 

Deep  discharge 

battery protection is ON when the P

BAT 

jumper is OFF.

 

8.  Mount  the  battery  in  the  battery  compartment  of  the  enclosure  (Fig.  3).  Connect  the  batteries  with  the  PSU 

paying special attention to the correct polarity.  

9.  Switch on the 230V AC supply. The corresponding LEDs on the power supply PCB should be ON: red AC and 

green AUX. The yellow LB LED should light up while charging. 

10.  Check  the  output  voltage  (the  power  supply  voltage  without  load  should  be  13,6

V ÷ 13,9V, 11V ÷ 13,8V while 

battery charging). If the voltage requires adjustment, use the V

ADJ

, potentiometer while monitoring the voltage at 

the AUX output of the power supply. 

11.  Check  the  current  consumption  of  the  receivers,  taking  into  account  the  battery  charging  current,  so  as  not  to 

exceed the total current efficiency of the PSU (section 1.1). 

12.  Close the cover after installing and checking the operation of the power supply. 

 

3. 

Power supply operation indication

 

3.1 Optical indication.  

 

The PSU is fitted with 3 LED lights at the front panel

:

 

 

 

 

 

Additionally, the PSU is fitted with 3 LED lights indicating the operating status: AC, LB and AUX at the PCB 

of the PSU: 

 

AC-  red  LED

:  is  permanently  illuminated  during  normal  operation  (AC  power  ON).  No  AC  power  is 

indicated by turning off the LED. 

 

LB- yellow LED

: indicates battery charging. The light intensity depends on the charging current. 

 

AUX

green LED:

 indicates DC power status at the PSU output. During normal operation, it is permanently 

illuminated. In case of short-circuit or output overload the LED is off

 
 

 

Содержание Blue Power PSBS 2012B

Страница 1: ...PSBS 2012B v 1 0 PSBS 13 8V 2A 7Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 4 from 03 11 2016 Supercedes edition 3 from 01 06 2016...

Страница 2: ...ate TABLE OF CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Instal...

Страница 3: ...8V 4x0 5A MPSBS 7Ah PSBS 2012B LB4 4x0 5A AWZ574 AWZ576 MPSBS 7Ah 4 Buffer power supply PSBS 13 8V 12V 2A MPSBS 7Ah PSBS 2012B RN250 13 8V 12V MPSBS 7Ah 5 Buffer power supply PSBS 13 8V 12V 2x1A MPSB...

Страница 4: ...ustment FBAT fuse in the battery circuit F3 15A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical out...

Страница 5: ...Isolation transformer Printed Circuit Board see Table 1 Fig 2 TAMPER micro switch of tamper protection NC FMAINS fuse in the power supply circuit 230V T500mA 250V L N power supply connector 230V AC PE...

Страница 6: ...rrent limitation the FBAT melting fuse failure requires fuse replacement Surge protection varistors Deep discharge battery protection UVP U 10V 0 5V disconnection of battery terminal Tamper protection...

Страница 7: ...tween input circuit and output or protection circuit 100 M 500V DC Table 6 Operation parameters Environmental class II Operating temperature 10 C 40 C Storing temperature 20 C 60 C Relative humidity 2...

Страница 8: ...icating AC power failure PSU technical output indicating PSU failure LoB technical output indicating low battery voltage Optional installation of the MPSBS relay module changing technical outputs of t...

Страница 9: ...hort circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output indicating low battery voltage The output indicates low battery voltage Under...

Страница 10: ...ltage at the battery terminals drops below 10V 0 5V during battery assisted operation the batteries will be disconnected The battery protection is on when the PBAT jumper is off Caution It is not reco...

Отзывы: