4. Service and operation. 

 
4.1  Overload or short-circuit of the power supply output (SCP activation). 

            The AUX output of the PSU is protected against short-circuit by

 

PTC polymer fuse. If the power supply load 

current exceeds Imax. (110% ÷ 150% @ 25°C of the PSU power), automatic disconnection of the output voltage, 
indicated  by  switching  off  the  green  LED,  takes  place.  To  restore  the  voltage  at  the  output,  disconnect  the  load 
from the power supply output for approximately 1 minute. 
 

In case of a short-circuit at the AUX, BAT output or reverse battery connection, the F

BAT

 fuse in the battery 

circuit becomes permanently damaged. The voltage restoration at the BAT output requires fuse replacement. 

 

4.2  Running the PSU from the battery. 

 

The power supply is equipped with the button on the PCB allowing to run the PSU from the battery, when 

needed. To do that, press and hold the 

START

 button on the unit board for 1 second. 

 

4.3  Deep discharge battery protection UVP. 

The  power  supply  is  equipped  with  deep  discharge  battery  protection  (UVP).  If  the  voltage  at  the  battery 

terminals drops below 1

0V±0.5V during battery-assisted operation, the batteries will be disconnected. 

The battery 

protection is on when the P

BAT 

jumper is off.

 

 

Caution.  

It is not recommended to disable UVP since deep  discharge of the batteries reduces their ability to 
store energy, their capacity and lifetime. 

 
 

4.4  Maintenance. 

All  maintenance  procedures  can  be  performed  after  disconnecting  the  power  supply  from  the  power 

network.  The  PSU  does  not  require  any  specific  maintenance;  however,  its  interior  should  be  cleaned  with 
compressed air if used in dusty conditions. In case of fuse replacement, use only compatible replacement parts. 

 

 

 

 

WEEE LABEL 

 

Waste electrical and electronic equipment must not be disposed of with normal household waste. 

According to the European Union WEEE Directive, waste electrical and electronic equipment 

should be disposed of separately from normal household waste. 

 

 

CAUTION!

 

The power supply unit is adapted for cooperation with the sealed lead-acid batteries (SLA). After the operation period they must 

not be thrown but recycled according to the applicable law. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Pulsar sp. j.  

Siedlec 150,  32-744 Łapczyca, Poland 

Tel.  (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 

E-mail: 

[email protected]

[email protected]

 

http:// 

www.pulsar.pl

www.zasilacze.pl

 

Содержание Blue Power PSBS 2012B

Страница 1: ...PSBS 2012B v 1 0 PSBS 13 8V 2A 7Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 4 from 03 11 2016 Supercedes edition 3 from 01 06 2016...

Страница 2: ...ate TABLE OF CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Instal...

Страница 3: ...8V 4x0 5A MPSBS 7Ah PSBS 2012B LB4 4x0 5A AWZ574 AWZ576 MPSBS 7Ah 4 Buffer power supply PSBS 13 8V 12V 2A MPSBS 7Ah PSBS 2012B RN250 13 8V 12V MPSBS 7Ah 5 Buffer power supply PSBS 13 8V 12V 2x1A MPSB...

Страница 4: ...ustment FBAT fuse in the battery circuit F3 15A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical out...

Страница 5: ...Isolation transformer Printed Circuit Board see Table 1 Fig 2 TAMPER micro switch of tamper protection NC FMAINS fuse in the power supply circuit 230V T500mA 250V L N power supply connector 230V AC PE...

Страница 6: ...rrent limitation the FBAT melting fuse failure requires fuse replacement Surge protection varistors Deep discharge battery protection UVP U 10V 0 5V disconnection of battery terminal Tamper protection...

Страница 7: ...tween input circuit and output or protection circuit 100 M 500V DC Table 6 Operation parameters Environmental class II Operating temperature 10 C 40 C Storing temperature 20 C 60 C Relative humidity 2...

Страница 8: ...icating AC power failure PSU technical output indicating PSU failure LoB technical output indicating low battery voltage Optional installation of the MPSBS relay module changing technical outputs of t...

Страница 9: ...hort circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output indicating low battery voltage The output indicates low battery voltage Under...

Страница 10: ...ltage at the battery terminals drops below 10V 0 5V during battery assisted operation the batteries will be disconnected The battery protection is on when the PBAT jumper is off Caution It is not reco...

Отзывы: