PSBS 2012B
v.1.0
PSBS 13,8V/2A/7Ah/OC
Buffer switch mode power supply unit
with technical outputs.
EN**
Edition: 4 from 03.11.2016
Supercedes edition: 3 from 01.06.2016
Страница 1: ...PSBS 2012B v 1 0 PSBS 13 8V 2A 7Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 4 from 03 11 2016 Supercedes edition 3 from 01 06 2016...
Страница 2: ...ate TABLE OF CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Instal...
Страница 3: ...8V 4x0 5A MPSBS 7Ah PSBS 2012B LB4 4x0 5A AWZ574 AWZ576 MPSBS 7Ah 4 Buffer power supply PSBS 13 8V 12V 2A MPSBS 7Ah PSBS 2012B RN250 13 8V 12V MPSBS 7Ah 5 Buffer power supply PSBS 13 8V 12V 2x1A MPSB...
Страница 4: ...ustment FBAT fuse in the battery circuit F3 15A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical out...
Страница 5: ...Isolation transformer Printed Circuit Board see Table 1 Fig 2 TAMPER micro switch of tamper protection NC FMAINS fuse in the power supply circuit 230V T500mA 250V L N power supply connector 230V AC PE...
Страница 6: ...rrent limitation the FBAT melting fuse failure requires fuse replacement Surge protection varistors Deep discharge battery protection UVP U 10V 0 5V disconnection of battery terminal Tamper protection...
Страница 7: ...tween input circuit and output or protection circuit 100 M 500V DC Table 6 Operation parameters Environmental class II Operating temperature 10 C 40 C Storing temperature 20 C 60 C Relative humidity 2...
Страница 8: ...icating AC power failure PSU technical output indicating PSU failure LoB technical output indicating low battery voltage Optional installation of the MPSBS relay module changing technical outputs of t...
Страница 9: ...hort circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output indicating low battery voltage The output indicates low battery voltage Under...
Страница 10: ...ltage at the battery terminals drops below 10V 0 5V during battery assisted operation the batteries will be disconnected The battery protection is on when the PBAT jumper is off Caution It is not reco...