Page
67
Failsafe
P808 Fail-safe Mode
By default, if a fail-safe condition occurs, then the display and the output are
held at their last
known
values until a valid reading is obtained.
If required, then you can change this so that the unit goes to
high
(100% of
span), or
low
(empty) as follows:
Option
Description
1 = Known (Default)
Remain at the last
known
value
2 = High
Will fail to the
high
value (100% of Span).
3= Low
Will fail to the
low
value (empty)
See Also P218 (RL1), P228 (RL2) - Relay Fail-safe and P840 Output Fail-safe
Important Information
In the event of a
fail-safe
condition occurring, when the PC
Handheld Communicator or the optional Handheld Communicator,
are connected to the unit, or the optional on board display is fitted
the Display and Output can be configured to fail to a condition
which is independent of each other. To set independent
Output
Failsafe
see
P840.
P809 Fail-safe Time
In the event of a fail-safe condition the failsafe timer determines the time
before fail-safe mode is activated.
Default = 1min.
If the timer activates, the unit goes into
fail-safe
, as determined by
P808
(
Display
),
P218, 228
(
Relays
) and
P840
(
Output
). When this happens, if the
PC Handheld Communicator or the optional Handheld Communicator, are
connected to the unit, or the optional on board display is fitted, you will see
the message “
Failed Safe
!” on the display, along with a message explaining
why (lost echo or transducer fault, for example)
When a valid measurement is obtained then the display and output will be
restored and the timer is reset.