To program the
blackbox
for this
Example,
proceed as follows.
Access the
Program Mode
Key in the
passcode
1997
and press
ENTER
Using the menu system access the parameters, as detailed below, and select
the relevant options and
ENTER.
Top Level
Menu
Sub Menu
Parameter Detail
Selected
Value
Application
Operation
P100 Mode
2 = Level
P101 Xducer
2 = dB6
Distances
P104 Measnt Units
4 = feet
P105 Empty Level
15.0
P106 Span
13.5
Relays
Relay 1
P210 Relay 1 Type
2 = Control
P211 R1Function
1 = General
P212 R1 ID
2 = Alternate
P213 R1 Set 1
4.0
P214 R1 Set 2
1.5
Relay 2
P220 Relay 1 Type
2 = Control
P221 R1Function
1 = General
P222 R1 ID
2 = Alternate
P223 R1 Set 1
6.0
P224 R1 Set 2
1.5
Programming is now complete and the unit can be returned to the run mode,
press
CANCEL
until
Run Mode?
Is displayed on the display press
ENTER
,
and the
blackbox
will return to the
Run Mode
.
Note
The mA output will be automatically set to the value of P106 Span,
with 0 or 4 mA being representative of 0% of Span (zero level) and
20mA 100% of Span (Full level).