Example 2 Alternating Control (pump down)
A sump is typically used to temporarily hold water or effluent, and when the
level reaches a specific point, the sump is pumped down, with the fluid being
transferred to another process.
empty distance (P105), 15.0 feet
100%, span (P106), 13.5 feet
(output = 20mA)
pump 1+2 off (P214, 224), 1.5 feet
0% , empty level (output = 4mA)
pump 2 on (P 223), 6.0 feet
pump 1 on (P 213), 4.0 feet
In this example a
blackbox
with dB6 is being used to control pumps on a
pump down
application, there are two pumps, and the
duty
pump is to be
alternated
between the pumps.
This will operate as follows. During normal operation,
pump 1
will come on
at 4.0 feet, and pump down to 1.5 feet. The setpoints are then shifted to
pump
2
, which will come on first next time.
During peak periods, when
pump 1
cannot cope,
pump 1
will come on at 4.0
feet,
pump 2
will come on at 6.0 feet, and pump down to 1.5 feet. The
setpoints are then shifted to
pump 2
, which will come on
first next time
.
The 4 to 20mA output will be representative of level.