Page
56
Alarm ID
Description
Setpoints
6= In bounds
Relay goes “ON” if
value is inside the zone
between the two
setpoints.
Relay Setpoints,
P2
1
3, 2
2
3 and
P2
1
4, 2
2
4 can be
set in any order as
the unit ‘knows’
that you are setting
an inbounds alarm.
7= Out of bounds
Relay goes “ON” if
value is outside the zone
between the two
setpoints.
Relay Setpoints
P21
3
, 2
2
3 and
P2
1
4, 2
2
4 can be
set in any order as
the unit ‘knows’
that you are setting
an out of bounds
alarm.
The
fourth parameter
and the
fifth parameter
for each relay set the
Alarm
“
ON
” and “
OFF
” points. For a
high alarm
the “
ON
” is set
higher than
“
OFF
”. For
low alarm,
then “
ON
” is set
lower than
“
OFF
”. See the
appropriate
alarm ID,
table (
P212, 222
) for further information.
When P211, P221 = 3 (Loss of Echo) or 4 (Loss of Clock)
This parameter has no function and will not be displayed.
When P211, P221 = 1 (Level) or 2 (Temperature)
P213, P223 - Relay Setpoint 1
Determines the “
ON
” or “
OFF
” point for the alarm according to the
ID
selected.
P214, P224 - Relay Setpoint 2
Determines the “
ON
” or “
OFF
” point for the alarm according to the
ID
selected.