2. Technical description. 
 

2.1. General description. 
The  buffer  power  supply  has  been  designed  in  accordance  with  the  requirements  of  the  PN-EN  50131-6 

standard, grade 1÷3 and II environmental class. It is intended for an uninterrupted supply to alarm system devices 
requiring stabilized voltage of 12V/DC (+/-15%). 

Depending  on  a  required  protection  level  of  the  alarm  system  in  the  installation  place, the  PSU  efficiency 

and the battery charging current ought to be measured as follows:   

 
* Grade 1, 2 - standby time 12h  

 

 

 

 

Output voltage 1,4A + 0,6A battery charge 

 
** Grade 3 - standby time 30h if the faults of the  main power source are reported to the Alarm Receiving 
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1). 
 

 

 

Output voltage 0,56A + 1,5A battery charge 

 

 

      

-  standby  time  60h  if  the  faults  of  the  main  power  source  are  reported  to  the  Alarm  Receiving 

Centre - ARC (in accordance with 9.2 – PN-EN 50131-1). 
 

 

 

Output voltage 0,28A + 1,5A battery charge 

 
***  General  use  –  if  the  PSU  is  not  mounted  within  an  installation  which  is  PN-EN-50131 compliant,  the 
acceptable current efficiency amounts to: 

 

 

 

 

 

1. Output voltage 2A + 0,2A battery charge 

 

 

 

2. Output voltage 1,6A + 0,6A battery charge 

                                      3. Output voltage 1,2A + 1A battery charge 
                                      4. Output voltage 0,7A + 1,5A battery charge 
 

                                               Total current of the rec battery: 2,2A max. 

 In case of power decay, a battery back-up is activated immediately. The PSU is housed in a metal 

enclosure (colour: RAL 9005 - black) which can accommodate a 17Ah/12V battery. It features micro switches that 
indicate unwanted door opening (faceplate) and detaching from the mounting surface. 

 
2.2. Block diagram. 
The  PSU  has  been  manufactured  based  on  a  high-duty  system  of  DC/DC  converter.  It  features  a 

microprocessor-based  operation  control,  responsible  for  full  diagnostics  of  the  PSU  and  battery 
parameters.

 

Fig. 1. Block diagram of the PSU. 

Содержание BLACK POWER PSBEN 2012C

Страница 1: ...PSBEN 2012C v 1 0 PSBEN 13 8V 2A 17Ah EN Buffer switched mode power supply unit EN Edition 3 from 20 11 2012 Supersedes the 2 from 14 09 2012 edition...

Страница 2: ...0 4 4 STANDBY TIME 11 4 5 BATTERY CHARGING TIME 11 4 6 OPERATION WITHOUT A BATTERY 11 5 REMOTE MONITORING OPTION WI FI ETHERNET RS485 USB 12 5 1 COMMUNICATION IN WI FI WIRELESS NETWORK 12 5 2 COMMUNIC...

Страница 3: ...OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical output indicating AC powe...

Страница 4: ...ource are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 1 5A battery charge General use if the PSU is not mounted within an installation which is...

Страница 5: ...isted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZER acoustic indicator 8 FBAT fuse...

Страница 6: ...L N 230V AC power connector PE connector 6 Battery connectors positive BAT red negative BAT black 7 Grip of tamper resistance Fig 3 The view of the PSU 3 Operating status indication 3 1 Control panel...

Страница 7: ...LED indicates battery failure green LED indicates power at the AUX output of the PSU three yellow LEDs indicate battery charging level Fig 5 Menu of the display FLt PSU fault memo 30 last events Io A...

Страница 8: ...tion Battery fault undercharged battery 3 2 signals per 10s battery assisted operation Low level of battery charge 4 Fast signals battery assisted operation The PSU will be disconnected due to the bat...

Страница 9: ...l If voltage appears at the EXT IN input it will cause generating a PSU failure storing the information about the event in the internal memo and sending the signal about the failure to the PSU FLT out...

Страница 10: ...is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing energy lowers its capacity and shortens its durability 4...

Страница 11: ...5A battery charge 4 5 Battery charging time The PSU has a battery circuit charged with direct current The current selection is done via IBAT jumpers The table below shows how long it takes to charge a...

Страница 12: ...ge of wireless communication is lack of additional cords and fast development or modification of the network s structure Fig 10 WI FI communication with the use of the WI FI INTW interface 5 2 Communi...

Страница 13: ...B TTL INTU needs to be used This interface allows direct connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM port Fig 13 KUSB TTL communication...

Страница 14: ...eneral use Io 2A 0 2A battery charge Io 1 6A 0 6A battery charge Io 1 2A 1A battery charge Io 0 7A 1 5A battery charge Output voltage setting escalation and keeping time 20ms 30ms 10ms Output voltage...

Страница 15: ...an be led Convectional cooling Table 8 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input network cir...

Страница 16: ...s of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 15 Fixing a tamper grip 2 Connect the power cables 230Vac to L N te...

Страница 17: ...ivers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status change into Hi Z high impedance by so...

Страница 18: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in t...

Страница 19: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...

Отзывы: