  4.4. Standby time.  
The  standby  time  during  batter-assisted  operation  depends  on:  battery  capacity,  battery charge  level  and 

load current. In order to keep the standby time, the current  drawn from the PSU  during  battery-assisted operation 
should be limited. Characteristics for a 17Ah/12V SLA: 

 
Grade 1, 2 - standby time 12h   

 

 

 

 

Output current 1,4A + 0,6A battery charge 

 
Grade 3 - standby time 30h if the faults of the main power source are reported to the Alarm Receiving 
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1). 
 

 

 

Output current 0,56A + 1,5A battery charge 

 

 
 - standby time 60h if the faults of the main power source are reported to the Alarm Receiving 

Centre - ARC (in accordance with 9.2 – PN-EN 50131-1). 
 

 

 

Output current 0,28A + 1,5A battery charge 

 
 
 

4.5. Battery charging time. 

 

The  PSU  has  a  battery  circuit  charged  with  direct current.  The  current  selection  is  done via 

I

BAT

  jumpers. 

The  table  below  shows  how  long  it  takes  to  charge  a  (fully  discharged)  battery  up  to  min.  80%  of  its  nominal 
capacity.  

Table 5. Battery charging time. 

17Ah

 battery charging time

  

up to capacity of 0,8*C 

Charging 

current [A] 

Configuration of 

I

BAT 

jumper 

10h12m 

1,5 

J1= 

, J2= 

, J3= 

 

15h18m 

J1= 

, J2= 

  J3= 

 

25h30m 

0,6 

J1= 

, J2= 

  J3= 

 

0,2 

J1= 

, J2= 

  J3= 

 

 
 

4.6 Operation without a battery. 
In case of an expected PSU operation without an attached battery, make a necessary configuration of 

jumpers: 

 

 

 

In this mode the automation system allows adjustments of PSU’s output voltage without indicating a failure 

connected with working of the battery. 

 

 
CAUTION. During operation without battery assistance the PSU does not perform any parameter 
control that monitors its proper operation. Therefore, this mode ought to be chosen thoughtfully. 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание BLACK POWER PSBEN 2012C

Страница 1: ...PSBEN 2012C v 1 0 PSBEN 13 8V 2A 17Ah EN Buffer switched mode power supply unit EN Edition 3 from 20 11 2012 Supersedes the 2 from 14 09 2012 edition...

Страница 2: ...0 4 4 STANDBY TIME 11 4 5 BATTERY CHARGING TIME 11 4 6 OPERATION WITHOUT A BATTERY 11 5 REMOTE MONITORING OPTION WI FI ETHERNET RS485 USB 12 5 1 COMMUNICATION IN WI FI WIRELESS NETWORK 12 5 2 COMMUNIC...

Страница 3: ...OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical output indicating AC powe...

Страница 4: ...ource are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 1 5A battery charge General use if the PSU is not mounted within an installation which is...

Страница 5: ...isted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZER acoustic indicator 8 FBAT fuse...

Страница 6: ...L N 230V AC power connector PE connector 6 Battery connectors positive BAT red negative BAT black 7 Grip of tamper resistance Fig 3 The view of the PSU 3 Operating status indication 3 1 Control panel...

Страница 7: ...LED indicates battery failure green LED indicates power at the AUX output of the PSU three yellow LEDs indicate battery charging level Fig 5 Menu of the display FLt PSU fault memo 30 last events Io A...

Страница 8: ...tion Battery fault undercharged battery 3 2 signals per 10s battery assisted operation Low level of battery charge 4 Fast signals battery assisted operation The PSU will be disconnected due to the bat...

Страница 9: ...l If voltage appears at the EXT IN input it will cause generating a PSU failure storing the information about the event in the internal memo and sending the signal about the failure to the PSU FLT out...

Страница 10: ...is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing energy lowers its capacity and shortens its durability 4...

Страница 11: ...5A battery charge 4 5 Battery charging time The PSU has a battery circuit charged with direct current The current selection is done via IBAT jumpers The table below shows how long it takes to charge a...

Страница 12: ...ge of wireless communication is lack of additional cords and fast development or modification of the network s structure Fig 10 WI FI communication with the use of the WI FI INTW interface 5 2 Communi...

Страница 13: ...B TTL INTU needs to be used This interface allows direct connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM port Fig 13 KUSB TTL communication...

Страница 14: ...eneral use Io 2A 0 2A battery charge Io 1 6A 0 6A battery charge Io 1 2A 1A battery charge Io 0 7A 1 5A battery charge Output voltage setting escalation and keeping time 20ms 30ms 10ms Output voltage...

Страница 15: ...an be led Convectional cooling Table 8 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input network cir...

Страница 16: ...s of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 15 Fixing a tamper grip 2 Connect the power cables 230Vac to L N te...

Страница 17: ...ivers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status change into Hi Z high impedance by so...

Страница 18: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in t...

Страница 19: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...

Отзывы: