Pulsar BLACK POWER PSBEN 2012C Скачать руководство пользователя страница 15

www.pulsar.pl   

 

 

 

PSBEN2012C   

 

 

 

 
 

15 

EXT IN technical input 

Voltage ’on’ –  10

÷

30V DC 

Voltage ’off’ –  0

÷

2V DC 

Level of galvanic isolation: 1500V

RMS

 

Optical indication: 

- LEDs on the PSU’s pcb, 
- LED panel 

  output current readings 

  output voltage readings 

 

failure codes with history

 

Acoustic indication: 

- piezoelectric indicator ~75dB /0,3m, switchable via jumper

 

F

BAT 

fuse

 

F

MAIN 

fuse 

F 3,15A / 250V 
T 0,5A / 250V

 

 

 

Table 7. Mechanical specifications.                                                                                                                              

Enclosure dimensions 

300 x 300 x 98  (305 x 305 x 90+8) (WxHxD) [mm] (+/- 2) 

Fixing 

272x 247 x 

Φ

 6 x4 (WxH) 

Fitting battery 

17Ah/12V (SLA) max. 

Net/gross weight 

4,1/4,3kg 

Enclosure  

Steel plate DC01  1mm, colour RAL 9005 (black) 

Closing 

Cheese head screw x2 (at the front), lock assembly possible 

Connectors 

Supply: 

Φ

0,63÷2,50 (AWG 22-10) 

Outputs : 

Ф

0,51÷2 (AWG 24-12), battery outputs BAT: 6,3F-2,5, 30cm 

TAMPER output: wires, 25cm 

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led. 
Convectional cooling. 

 

 

Table 8. Operation safety. 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input (network) circuit and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
500  V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC  

 
Table 9. Operating specifications. 

Operating temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 

Table 10. PSU’s factory settings. 

Indication time of EPS network loss  

5s 

Battery charging current 

0,6A 

Battery presence 

YES (battery present) 

Battery test 

YES (activated) 

Deep discharge battery protection UVP 

YES (battery protected) 

Communication address  

Transmission 

19.2k 8E1 

 
 
 
 
 
 
 

 

 
 

Содержание BLACK POWER PSBEN 2012C

Страница 1: ...PSBEN 2012C v 1 0 PSBEN 13 8V 2A 17Ah EN Buffer switched mode power supply unit EN Edition 3 from 20 11 2012 Supersedes the 2 from 14 09 2012 edition...

Страница 2: ...0 4 4 STANDBY TIME 11 4 5 BATTERY CHARGING TIME 11 4 6 OPERATION WITHOUT A BATTERY 11 5 REMOTE MONITORING OPTION WI FI ETHERNET RS485 USB 12 5 1 COMMUNICATION IN WI FI WIRELESS NETWORK 12 5 2 COMMUNIC...

Страница 3: ...OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical output indicating AC powe...

Страница 4: ...ource are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 1 5A battery charge General use if the PSU is not mounted within an installation which is...

Страница 5: ...isted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZER acoustic indicator 8 FBAT fuse...

Страница 6: ...L N 230V AC power connector PE connector 6 Battery connectors positive BAT red negative BAT black 7 Grip of tamper resistance Fig 3 The view of the PSU 3 Operating status indication 3 1 Control panel...

Страница 7: ...LED indicates battery failure green LED indicates power at the AUX output of the PSU three yellow LEDs indicate battery charging level Fig 5 Menu of the display FLt PSU fault memo 30 last events Io A...

Страница 8: ...tion Battery fault undercharged battery 3 2 signals per 10s battery assisted operation Low level of battery charge 4 Fast signals battery assisted operation The PSU will be disconnected due to the bat...

Страница 9: ...l If voltage appears at the EXT IN input it will cause generating a PSU failure storing the information about the event in the internal memo and sending the signal about the failure to the PSU FLT out...

Страница 10: ...is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing energy lowers its capacity and shortens its durability 4...

Страница 11: ...5A battery charge 4 5 Battery charging time The PSU has a battery circuit charged with direct current The current selection is done via IBAT jumpers The table below shows how long it takes to charge a...

Страница 12: ...ge of wireless communication is lack of additional cords and fast development or modification of the network s structure Fig 10 WI FI communication with the use of the WI FI INTW interface 5 2 Communi...

Страница 13: ...B TTL INTU needs to be used This interface allows direct connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM port Fig 13 KUSB TTL communication...

Страница 14: ...eneral use Io 2A 0 2A battery charge Io 1 6A 0 6A battery charge Io 1 2A 1A battery charge Io 0 7A 1 5A battery charge Output voltage setting escalation and keeping time 20ms 30ms 10ms Output voltage...

Страница 15: ...an be led Convectional cooling Table 8 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input network cir...

Страница 16: ...s of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 15 Fixing a tamper grip 2 Connect the power cables 230Vac to L N te...

Страница 17: ...ivers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status change into Hi Z high impedance by so...

Страница 18: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in t...

Страница 19: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...

Отзывы: