- green LED  (Fig.2, element 3) indicates battery voltage level. Under normal status (U

BAT

 > 11,5V) the diode is 

permanently illuminated. In case of decrease of battery voltage (U

BAT

 < 11,5V) the diode is off.

 

 

3.2 Technical outputs

 

The PSU has indication outputs: 
 

 

FAC - absence of AC supply output

:  

-  OC  type  output  that indicates  AC  power  loss.  Under  normal  status,  with  230V  AC  supply,  the  output  is 
connected  to  ground  (L  level  –  0V).  In  case  of  power  loss,  the  PSU  will  switch  the  output  into  high 
impedance state hi-Z after approx. 10s. 

relay output indicating the absence of AC supply. In case of power loss, the PSU module will switch the 

relay contacts after approx. 10 seconds. 

 

CAUTION!

 In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 

power (AC power failure). 
 
 

 

 

FPS – technical output indicating absence of DC voltage at the PSU

-    OC  type  output  indicating  the  PSU  failure.  In  normal  state  (during  correct  operation)  the  output  is 
connected to ground (L level – 0V). In case of absence of DC voltage at the output (e.g. short circuit), the 
output is switched into high impedance state – hi-Z. 

     - relay output. In case of a failure, the contacts of the relay change over. 

 
 

CAUTION

!

  In  the  Fig.2.  the  set  of  contacts  shows  a  potential-free  status  of  the  relay  which 

corresponds to a state with no DC power (PSU failure). 

 

 

FLB – technical output indicating battery voltage

:  

- OC type output. Under normal status (U

BAT

 > 11,5V) the output is connected to ground (L level – 0V). In 

case of decrease of battery voltage (U

BAT

 < 11,5V) the output is switched into high impedance state – hi-Z. 

      -  relay output. In case of a battery voltage drop U

BAT

 < 11,5V, the contacts of the relay change over. 

 
 
CAUTION

!

 In the Fig.2. the set of contacts shows a potential-free status of the relay which 

corresponds to a state with low battery level (U

BAT

 <11,5V). 

 

 

Fig. 4. Electrical diagram of OC outputs. 

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU module output 

In case of an overload or a short circuit at the PSU output, the output voltage is automatically cut off. The 

voltage is restored automatically after removing the failure (overload). 

 
4.2 Battery-assisted operation.  

In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

 

 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the 

battery-assisted operation, reducing voltage below 9,5V at the battery terminals will cause 
battery disconnection. 

 
4.3 Maintenance 

Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power  supply  network.  The  PSU  does  not  require  performing  any  specific  maintenance  measures.  However,  in 
case of significant dust ingress, it is recommended to clean the PSU with compressed air. 

 

Содержание ADOC551230

Страница 1: ...ADOC551230 v 1 0 ADOC 13 8V 3A OC Enclosed buffer switch mode power supply unit with automatic operation control EN Edition 1 from 29 10 2013 Supercedes edition...

Страница 2: ...NTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure...

Страница 3: ...oltage 4 FAC AC absence technical output relay type 5 FPS output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output O...

Страница 4: ...circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection fuse Surge prote...

Страница 5: ...C Storage temperature 20 C 85 C Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrat...

Страница 6: ...tput connectors of the power supply positive pole is marked as V negative pole as COM 5 Connect the technical outputs to the central or other device 6 Connect the battery to proper output connectors o...

Страница 7: ...ich corresponds to a state with no DC power PSU failure FLB technical output indicating battery voltage OC type output Under normal status UBAT 11 5V the output is connected to ground L level 0V In ca...

Страница 8: ...epair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty term...

Отзывы: