GREEN POWER CCTV PoE

 

 

 

 

 

Diagram 1.

 

Maximum permissible output current depending on ambient temperature.

 

 
2.  Installation. 

 

2.1. Requirements. 

 

The  buffer  PSU  should  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable and  required  for  a  given  country)  for  230V/AC  and  low-voltage  installations. The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, no condensation) and temperature range from -10°C up to +40°C. The  power  supply  sh ould  
operate  in  a  vertical position in order to provide free and  convectional  air  flow  through ventilating holes of the 
enclosure.  

 

 
During normal operation, the total current drawn by the device should not exceed  
I = 8x0,3A. Maximum battery charging current is 0,2 A. Total current of the rec 

battery is max 2,6 A. 

The    power    supply    is    designed    for    a    continuous    operation    and    is    not    equipped    with    a  

power-switch.  Therefore,  an  appropriate  overload  protection  in  the  power  supply  circuit  should  be  provided. 
Moreover, the user should be informed how to disconnect the power supply unit from the mains supply (usually by 
assigning an appropriate fuse in the fuse box).   The electrical system shall be made in accordance with applicable 
standards and regulations.  

The PSU is designed for 10Mbit/s and 100Mbit/s Ethernet network (so-called Fast Ethernet). However, it 

can  not  be  used  for  a  1000  Mbit/s  network  (so-called  Gigabit  Ethernet).  Connections  between  the  power 
supply and the camera can be done using UTP-3 cable (networks with data-rates up to 10 Mbit/s) or UTP-5 cable. 
Due to the lower resistance wiring, it is recommended (especially at large distances between the power supply and 
receivers) to use UTP-5 cable also for networks with data-rates up to 10 Mbit/s.  

 

2.2. Installation procedure. 
 

1. Before installation, cut off the voltage in the 230V power-supply circuit. 
2. Mount the PSU in a selected location and lead the connecting cables.  
3.  Connect  the  power  cables  (230V  AC)  to  L-N  terminals  of  the  PSU.  Connect  the  ground  wire  to  the  terminal 

marked with grounding symbol:

. Use a three-core cable (with a yellow and green PE  protection wire) to make 

the  connection.  The  power  cables  should  be  connected  to  the  appropriate  terminals  on  the  connection  board 
through the bushing.  

 

The shock protection circuit shall be done with a particular care: the yellow and green wire 

coat of  the  power  cable  should be connected to  the  terminal  marked  with  the  

  symbol  

in  the  PSU enclosure. Operation of the PSU without the properly made and fully operational 
shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  damage  to  the  equipment  or  an 
electric shock

 

 
 
 

Содержание 54V/8x03A/4x7Ah

Страница 1: ...POE084824B v 1 0 PoE 54V 8x0 3A 4x7Ah Switch mode buffer power supply unit for CCTV EN Edition 1 from 26 11 2013 Supersedes the edition GREEN POWER CCTV PoE...

Страница 2: ...aintenance 1 Technical description 1 1 General description The PSU is designed for supply of up to 8 webcams requiring stabilized voltage of 48V DC 15 The PSU supplies voltage of 54V DC and total curr...

Страница 3: ...ation input 3 F1 F8 fuses in the AUX1 AUX8 F500mA circuits 4 Jumper to select melting fuse or PTC polymer fuse 5 Green LED L1 L8 voltage indication at the AUX outputs during normal operation these LED...

Страница 4: ...black 6 TAMPER microswitch contacts of antisabotage protection NC Tab 2 Components of the PSU see Fig 3 1 4 Technical parameters electrical parameters Table 3 mechanical parameters Table 4 safety of...

Страница 5: ...ical parameters Table 4 Enclosure dimensions 300 x 407 x 126 mm WxHxD Mounting See Fig 3 Battery housing 4x7Ah 12V SLA max Net weight 4 71kg 5 01kg Enclosure DC01 steel plate 1 0mm RAL 9003 Closing Cy...

Страница 6: ...shall be made in accordance with applicable standards and regulations The PSU is designed for 10Mbit s and 100Mbit s Ethernet network so called Fast Ethernet However it can not be used for a 1000 Mbi...

Страница 7: ...red battery output 0V BAT cable black 9 Check the optical indication of the PSU status green LED light on the PoE module 10 Close the cover after installing and checking the operation of the power su...

Страница 8: ...ly Fig 6 Electrical diagram of the relay output CAUTION The arrangement of contacts at the figure 6 shows a potential free status of the relay which is equivalent to a state with no voltage at any of...

Страница 9: ...ration the battery will be disconnected 4 3 Maintenance All maintenance procedures can be performed after disconnecting the power supply from the power network The PSU does not require any specific ma...

Страница 10: ...service centre of the manufacturer 6 The repair period mentioned in point 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally...

Отзывы: