GREEN POWER CCTV PoE

 

 

 

 

Fig. 3. The view of the PSU. 

 

Component No. 

[Fig. 3] 

Description 

[1] 

The module of the switch mode PSU 

[2] 

LED light indicating correct operation of the switch mode PSU 

[3] 

V1 ADJ potentiometer – regulation of the power supply output voltage 

[4] 

PoE module 

[5] 

Connectors for connecting the batteries: +BAT = red, - BAT = black 

[6] 

TAMPER – microswitch (contacts) of antisabotage protection (NC) 

Tab. 2. Components of the PSU (see Fig. 3). 

 
 

1.4 Technical parameters. 
- electrical parameters (Table 3) 
- mechanical parameters (Table 4) 
- safety of use (Table 5) 
- operation parameters (Table 6) 

 Electrical parameters (Table 3). 

Mains supply 

88÷264V AC  

Current consumption 

1,5A@230V AC typ. 

PSU’s power 

140,3W max. 

Efficiency 

84% 

Output voltage 

44V÷ 54V DC – buffer operation 
37V÷54V DC – battery operation 

The adjustment range of the output voltage 

48÷58V DC 

Output current  

8 x 0,3 A +0,2A battery charging 

Содержание 54V/8x03A/4x7Ah

Страница 1: ...POE084824B v 1 0 PoE 54V 8x0 3A 4x7Ah Switch mode buffer power supply unit for CCTV EN Edition 1 from 26 11 2013 Supersedes the edition GREEN POWER CCTV PoE...

Страница 2: ...aintenance 1 Technical description 1 1 General description The PSU is designed for supply of up to 8 webcams requiring stabilized voltage of 48V DC 15 The PSU supplies voltage of 54V DC and total curr...

Страница 3: ...ation input 3 F1 F8 fuses in the AUX1 AUX8 F500mA circuits 4 Jumper to select melting fuse or PTC polymer fuse 5 Green LED L1 L8 voltage indication at the AUX outputs during normal operation these LED...

Страница 4: ...black 6 TAMPER microswitch contacts of antisabotage protection NC Tab 2 Components of the PSU see Fig 3 1 4 Technical parameters electrical parameters Table 3 mechanical parameters Table 4 safety of...

Страница 5: ...ical parameters Table 4 Enclosure dimensions 300 x 407 x 126 mm WxHxD Mounting See Fig 3 Battery housing 4x7Ah 12V SLA max Net weight 4 71kg 5 01kg Enclosure DC01 steel plate 1 0mm RAL 9003 Closing Cy...

Страница 6: ...shall be made in accordance with applicable standards and regulations The PSU is designed for 10Mbit s and 100Mbit s Ethernet network so called Fast Ethernet However it can not be used for a 1000 Mbi...

Страница 7: ...red battery output 0V BAT cable black 9 Check the optical indication of the PSU status green LED light on the PoE module 10 Close the cover after installing and checking the operation of the power su...

Страница 8: ...ly Fig 6 Electrical diagram of the relay output CAUTION The arrangement of contacts at the figure 6 shows a potential free status of the relay which is equivalent to a state with no voltage at any of...

Страница 9: ...ration the battery will be disconnected 4 3 Maintenance All maintenance procedures can be performed after disconnecting the power supply from the power network The PSU does not require any specific ma...

Страница 10: ...service centre of the manufacturer 6 The repair period mentioned in point 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally...