P930 Factory Defaults
This parameter resets all parameter values to the original Factory Set values
that were installed when the unit was tested before despatch to you.
To
reset
parameters, enter
1
and press
ENTER
, all parameters, except for the
mA trims, will be restored to the factory settings (including the DATEM trace)
and on completion Stor (Store) will be displayed after which you can ESC out
of this parameter and continue programming the IMP Lite for the required
application.
Test (tESt) Menu
P991 Hard Test
When this parameter is selected, the unit will test the following in turn.
•
Display
. All the segments on the LCD and the backlight are lit up, so
you can see if they all work. Press the
ENTER
button, to end the test.
•
Keys
. You should press each button, to confirm it works, with a counter
showing how many more buttons you must press. Press
ESC
last, as this
will show if all keys were pressed or not. If they were not, then an error
message is displayed.
P992 mA Out Test
This parameter will allow you to force a specified current on the mA output,
to test the equipment that it is connected to, and to make sure the unit is
working correctly. The figure you enter will be generated by the mA output.