background image

Safety notes 

(Fig. 1)

Read 
instructions!

Before working with this unit, read these instructions 
carefully and completely. Make sure that you have 
understood all the information (ask colleagues)! Comply 
with notes on the unit! 

Disconnect 
system from 
supply 
network

Before any installation, maintenance or modification 
work: 
Disconnect your system from the supply network. 
Ensure that it cannot be re-connected inadvertently!

Before start 
of operation:
Ensure 
appropriate 
installation

Warning! Improper installation/operation may impair 
safety and result in operational difficulties or complete 
failure of the unit.
The unit must be installed and put into service by appro-
priately qualified personnel. Compliance with the rele-
vant regulations (DIN, VDE or specific national 
regulations) must be ensured. Before operation is 
begun the following conditions must be ensured, in par-
ticular:
• Connection to mains supply in compliance with 

VDE0100 and EN50178.

• With stranded wires: all strands must be secured in 

the terminal blocks (potential danger of short circuit).

• Unit and power supply cables must be properly fused. 

A disconnecting device has to be provided for the end 
product to disengage unit and supply cables from 
supply mains if required.

• The non-fused earth conductor must be connected to 

the 

 terminal (protection class 1).

• All output lines must be rated for the power supply 

output current and must be connected with the cor-
rect polarity.

• Sufficient air-cooling must be ensured.

In operation:
No modifica-
tions!

As long as the unit is in operation: do not modify the 
installation! The same applies also to the secondary side. 
Risk of electric arcs and electric shock (fatal)! 

Only (dis)connect plug connectors when the power 
is off!

Convection 
Cooling

Do not cover

 any ventilation holes! 

Leave sufficient space

 around the unit 

for cooling

! See supplementary sheet 

"

Technical Data

"

.

Warning:
High voltage!
Stored energy!

The unit contains unprotected conductors carrying a 
lethal high voltage, and components storing substantial 
amounts of energy. 

Improper handling may result in 

an electric shock or serious burns!

• The unit must not be opened except by appropriately 

trained personnel! 

• Do not introduce any objects into the unit!
• Do not open the unit for at least 5 minutes after it has 

been disconnected from the mains on all poles! 

• Keep away from fire and water!

EN

Note

Fig. 1

Installation

Admissible area of 
application

This unit is a primary switched-mode power supply unit 

for use in 

panel-board installations or other building-in applications

 where 

a suitable mechanical enclosure shall be provided to fulfill the require-
ments for shock-hazard protection and/or protection from hazardous 
energy levels as well as for fire protection. It must only be installed 
and put into service by appropriately qualified personnel.

Mounting

Mounting

Permissible 

mounting positions:

 see Fig. 2

e

 (but: observe derat-

ing

d

). 

Keep free ventilation holes, leave space for cooling! 

Recommended respective distances: see supplementary sheet 
"Technical Data". 

Attachment
Snap on 
support rail
(vgl. Fig. 2)

vi) Tilt the unit slightly rearwards.
vii)Fit the unit over top hat rail.
viii)Slide it downward until it hits the stop.
ix) Press against the bottom front side for locking.
x) Shake the unit slightly to check the locking action

Front elements 

(Fig. 1)

Operation indicator 
(



)

Indicates whether the unit is working properly. Green LED is on in nor-
mal operation and goes out if overloaded.

Potentiometer

f

 (



)

Setting the output voltage

d

Connection / Internal fuse 

Connection

• Data for permitted loads, cable cross-sections and stripping as well 

as for external fusing: see the enclosed leaflet "Technical Data", 
sub heading "Connection to Mains" or "Output"

• Handling of the terminals: see Fig. 4
• Use only commercial cables designed for the indicated voltage and 

current values!

• With flexible cables: make sure that all cable strands are secured in 

the terminal.

• Suitable conductor terminal sleeves (ferrules) may be used.
• Ensure proper polarity at output terminals!

Grounding

Do not operate without PE connection!

 To comply with EMC 

and safety standards (CE mark, approvals), the unit must only be 
operated if the PE terminal (

) is connected to the non-fused 

earth conductor

• Secondary side is not earthed; if necessary the 

 or 

 terminal 

can be earthed optionally. 

Internal fuse

The internal input fuse protects the unit and must not be replaced by 
the user. In case of an internal defect, the unit must be returned to the 
manufacturer for safety reasons.

Removal

Removal

Detaching from the 
support rail

Before removal:

 Switch mains power off and disconnect your system 

from the supply network. 
See Fig. 6: push the slider downwards (unlock). Gently lift lower front 
edge of the unit (tipping) and remove.

Recycling

The unit contains elements which are suitable for recycling, and 
components which need specialist disposal. You are therefore 
requested to make sure that the unit will be recycled by the end of its 
service life. 

Remarks:
d) See enclosed leaflet "Technical Data" sub-heading "Connection to Mains" or "Output" for 

details.

e) unless there are other instructions either on the unit or in the enclosed leaflet "Technical 

Data"

f) Not available with all units
This is a general information leaflet for all units in the current range. With some units devia-
tions from the instructions described here are possible, 

therefore instructions in the 

"Technical data" leaflet enclosed always take priority.

  In case of doubt 

the German version applies.

EN

6

5

P

U

-32

7

.015.

00-1

0

D

/01/2

003

Содержание MiniLine MLY10.241

Страница 1: ...ribe el proceso de instalaci n y operaci n En caso de discrepancias tendr n prioridad las informaciones del suplemento Datos t cnicos De existir contradicciones ling sti cas regir la versi n alemana E...

Страница 2: ...Figuras 2c iv i ii iii Fig 1 Fig 2 Fig 3 Fig 5 Fig 4 2 1 PU 327 015 00 10D 01 2003 Figures Note Click Out 6mm 1a 1b 1c 2a 2b Note Note 3mm 7mm L N In 0 3 2 5 mm2 28 12 AWG 0 3 4 mm2 28 12 AWG 0 3 2 5...

Страница 3: ...nd den Brandschutz erf llen m ssen Installation und Inbetriebnahme d rfen nur durch entsprechend qualifizier tes Personal erfolgen Montage Einbau Zul ssige Einbaulage vgl Fig 2b aber Deratinga beachte...

Страница 4: ...and or protection from hazardous energy levels as well as for fire protection It must only be installed and put into service by appropriately qualified personnel Mounting Mounting Permissible mountin...

Страница 5: ...ontre les ten sions et ou les nergies dangereuses et la protection incendie L ins tallation et la mise en service ne doivent tre effectu es que par du personnel qualifi Montage Installation Position d...

Страница 6: ...ligrosos de tensi n as como de protecci n contra quemaduras La instalaci n y la puesta en servicio han de ser efectuadas por per sonal debidamente cualificado Montaje Montaje Posici n de montaje admis...

Страница 7: ...incendio L installazione e la messa in esercizio devono avvenire soltanto con l intervento di personale specializzato Montaggio Montaggio Posizioni di montaggio ammisibili vedere Fig 2n Osservare decl...

Страница 8: ...bui o ou outros revestimentos mec nicos que devem cum prir as exig ncias quanto prote o contra contato com altas tens es e ou energia e prote o contra inc ndio Somente t cni cos qualificados poder o...

Отзывы: