UZK12.261, UZO12.26
U-Series
B
ATTERY
M
ODULE
12V,
26AH
Mar. 2019 / Rev. 2.2a DS-UZK12.261
All parameters are typical values specified at, 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/10
5.
I
NTENDED
U
SE
This module is designed for installation in an enclosure and is intended for the general professional use such as in
industrial control, office, communication, and instrumentation equipment.
Do not use this module in equipment, where malfunction may cause severe personal injury or threaten human life.
6.
I
NSTRUCTIONS FOR
D
ISPOSAL OF THE
B
ATTERIES
Batteries must be completely discharged before replacement and can be returned to the supplier of the battery
module or the battery manufacturer for disposal.
Always dispose batteries through a recycling organization.
7.
I
NSTRUCTIONS FOR
B
ATTERY
S
TORAGE
Do not store batteries or battery modules at temperatures higher than 25°C or performance and lifetime may change.
Do not store discharged batteries. Keep batteries fully charged!
Charge retention is important to get the longest battery life. Stored batteries which are not fully charged age faster
then charged batteries.
Do not store batteries longer than 9 months without charging or performance and lifetime may change. Every 9
months or whenever the open circuit voltage (OCV) falls below 12.6V, the battery module should be charged. Apply a
charging voltage of 13.8V (at 25°C) for 72 hours. Batteries with an OCV below 12V must not be charged anymore and
must be disposed.
8.
I
NSTALLATION
I
NSTRUCTIONS
This device may only be installed and put into operation by qualified personnel.
Before initial use, check the last charging which is marked on the battery. If it is older than 9 month, replace the
battery.
Do not install the battery fuse until the installation work is complete.
This device does not contain serviceable parts, except the fuse or replacement battery. If malfunction should occur
during installation or operation, first check the fuse and battery for proper functionality. If the unit is damaged or if
the malfunction continues, immediately turn power off and send device to the factory for inspection.
Replacement fuses must be of the same type or an UL listed fuse with the same nominal value and characteristics.
Do not short-circuit the battery poles or power wires and always check correct battery polarity.
Mount the device onto a flat surface. Do not install the battery module upside down.
Place the battery module in a cool area inside a cabinet.
Install the device in an enclosure providing protection against electrical, mechanical and fire hazards. Ensure sufficient
ventilation by following the requirements of the EN 50272-2.