background image

 

 

PISA11.CLASS2

 

 

 

PISA11-Series 

P

ROTECTION 

M

ODULE 

24V,

 

4

 

O

UTPUTS

 

 

 

 

P

ROTECTION 

M

ODULE

 

ƒ

 

One Input and Four Current Controlled Outputs 

ƒ

 

NEC Class 2 Compliant Outputs 

ƒ

 

Ensures Sufficient Supply Voltage for Critical Loads 
even in the Event of an Fault 

ƒ

 

Protects Small Cable Sizes against Overload 

ƒ

 

Hassle-free Turn-on of Loads with Large Input 
Capacitors 

ƒ

 

Wide Temperature Range between -25°C and +70°C 

ƒ

 

On/Off Function of Outputs 

ƒ

 

Compact Design, Width only 45mm 

ƒ

 

Remote Monitoring and Control Functions  

ƒ

 

3 Year Warranty 
 

 

 

1/19

G

ENERAL 

D

ESCRIPTION

 

This protection module fulfills two basic functions. First it 
distributes the current of a large (non NEC Class 2) power 
source to four NEC CLASS 2 output channels and therefore 
allows for a simpler wiring method and easier approval 
process of the entire machine. The second function is to 
permit only so much current on the outputs that the input 
voltage of this unit (which corresponds to the output 
voltage of the power supply) does not fall below 21V. 

This ensures a safe and an uninterrupted supply voltage for 
sensitive equipments, such as PLCs, controls or sensors, when 
they are 
connected 
directly to the 
same power 
supply as the 
PISA module. 
Less critical 
loads that are 
not affected to short voltage interruptions or that could 
even be the cause of a fault on the 24V power supply are 
connected to one of the four NEC CLASS 2 output channels 
of the PISA module. 

 

S

HORT

-

FORM 

D

ATA

 

 

Input voltage 

DC 24V 

 

Input voltage 
range 

18 - 30V 

 

Input current 

typ. 43mA 

At no load 

Number of outputs  4 

 

Output currents 

4x 3.7A at 24V 
4x 3.2A at 28V 

 

Input voltage 
protection levels 

typ. 21.4V 

 

Temperature range -25°C to +70°C 

Operational 

 

-40°C to +85°C 

Storage 

Type of current 
limitation 

Active current limitation followed 
by a shutdown 

Dimensions 45x75x91mm 

*) 

WxHxD 

Non NEC CLASS 2 Load

DC 24V

Power

Supply

NEC CLASS 2 Circuit 2

NEC CLASS 2 Circuit 3

NEC CLASS 2 Circuit 4

NEC CLASS 2 Circuit 1

A1

A2

A4

A3

PISA Protection Module

Safeguard

   *)  Add 13mm in depth for signal connector. 

 

 
 

O

RDER 

N

UMBERS

 

 

Protection 

PISA11.CLASS2

 

4x NEC CLASS 2 

module  

outputs

 

 
 

M

ARKINGS

 

 

IND. CONT. EQ.

 

UL 508

 

 

UL 60950-1

 

 

UL 2367

 

 

IEC 60950-1

 

NEC CLASS 2 

 

EMC, LVD

 

ATEX 

II 3G EX nA nC IIC T4

 

 

Class I Div 2, Pending

 

 

Feb. 2012 / Rev. 1.3  DS-PISA11.CLASS2 - data sheet - 
All parameters are specified at 24Vdc input, 25°C ambient temperature and a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278-0    Germany 

Содержание Dimension PISA11 Series

Страница 1: ...n they are connected directly to the same power supply as the PISA module Less critical loads that are not affected to short voltage interruptions or that could even be the cause of a fault on the 24V...

Страница 2: ...6 1 ZM3 WALL Wall Mounting Bracket 19 The information presented in this document is believed to be accurate and reliable and may change without notice The housing is patent by PULS US patent No US D44...

Страница 3: ...ly so much current that the input voltage does not drop below 21V In case the input voltage would fall below this value e g due to overloads too small of a power supply or high inrush currents such as...

Страница 4: ...n power off before working on the device Protect against inadvertent re powering Make sure that the wiring is correct by following all local and national codes Do not modify or repair the unit Do not...

Страница 5: ...see Fig 5 1 output 3 nom 3 7A 3 2A see Fig 5 1 output 4 nom 3 7A 3 2A see Fig 5 1 All 4 outputs together nom 14 8A 12 8A Output current limitation min 16 6A 16 6A typ 19 9A 19 9A max 23 6A 23 6A Volt...

Страница 6: ...d output current At 2 times the rated current typ 1s at 7 4A At short circuit typ 10ms The timer for shutdown starts immediately once the rated current levels are exceeded All output channels will shu...

Страница 7: ...All four outputs will shutdown simultaneously Shutdown times for a short circuit condition across the outputs can be found in Fig 6 2 Fig 6 2 Active current limitation Period of time in current limit...

Страница 8: ...al values are defined with an additional resistive load See also the parameter list below the table Permissible Capacitors PISA11 CLASS2 Per channel 58mF 14mF All four outputs together typ 58mF min 14...

Страница 9: ...max 10Vdc reset Galvanic isolation nom 500Vac Test voltage signal path to power path 10 SYNCHRONIZATION OF MULTIPLE PISA MODULES If multiple PISA modules are used on the same power supply it is recomm...

Страница 10: ...his feature is also called return voltage immunity or resistance against Back E M F Electro Magnetic Force The protection module is resistant and does not show malfunctioning when a load feeds back vo...

Страница 11: ...ulated according to the capacitor s manufacturer specification The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value...

Страница 12: ...rotection function of the input voltage protection circuit all other modules will shutdown too This avoids a false interpretation of which output channel caused the problem If the cause for the shutdo...

Страница 13: ...a Use NEC Class 2 rated wires for the output b Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and minimum 75 C for ambient up to 60...

Страница 14: ...ge voltage on input lines EN 61000 4 5 DIN Rail 500V 1kV 500V 1kV Criterion A Criterion A Surge voltage on output lines EN 61000 4 5 DIN Rail 500V 1kV 500V 1kV Criterion A Criterion A Surge voltage on...

Страница 15: ...y III IEC 62103 EN 50178 altitudes up to 2000m II for altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not conductive Operational temperature is the same as the ambient temperatu...

Страница 16: ...F signal input and input output voltage are 1 3mm The following dielectric strength tests were conducted Fig 20 1 Dielectric strength A B C Type test 60s 500Vac 500Vac 50Vac Factory test 5s 500Vac 500...

Страница 17: ...rrent Protector Component Recognition UL Category QVRQ2 E File E342020 ANSI ISA 12 12 01 2007 Class I Div 2 Pending LISTED for use in Hazardous Location Class I Div 2 T4 Groups A B C D systems NRTL C...

Страница 18: ...r PBDE Polychlorinated Diphenylether PCDE Polydibromphenyl Oxyd PBDO Cadmium Asbestos Mercury Silicia 24 READ OUT OF THE SOFTWARE REVISION LEVEL PISA utilizes a microcontroller with a dedicated firmwa...

Страница 19: ...AL DIMENSIONS AND WEIGHT Weight 120g 0 26lb DIN Rail Use 35mm DIN rail according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN rail height must be added to the unit depth to calculate t...

Отзывы: