Specifications:
Temperature Monitor Range:
32.2°F to 99.9°F (0.0°C to 37.7°C)
Setpoint Range:
60.0°F to 85.0°F (15.5°C to 29.5°C)
*Setpoint:
72°F (22°C)
*Comfort Limits:
65.0°F (18.5°C) cooling
85.0°F (29.5°C) heating
Display Format:
Liquid Crystal Display (LCD)
Backlight:
EL blue green
Sampling Rate:
Every 15 seconds
Accuracy:
± 1°F (0.5°C)
Power Source:
24VAC/DC (20 minimum to 32 maximum)
Load Rating:
1.5 amps per load circuit
*Fan Control: Selectable:
Auto cycle, Low, Medium, High
Heat/Cool Control:
1 heat and 1 cool circuit (see system function)
*Economy Limits:
Maintains room temperature between 60.0°F and 85.0°F
(15.5°C and 29.5°C) when thermostat is in economy (ECON) mode
*Fan Purge Timer:
30 seconds
Anti-short Cycle:
3 minute hold in no call state at all times
*Cycle Rate:
8 cycles per hour
* Differential:
0.4°F
* Display Mode:
Setpoint temperature
* System Function:
Heat and Cool
*See Field Programming Instructions
Application:
This thermostat is a 24 volt heating and cooling digital temperature
control designed to operate 2 or 4-pipe fan coil systems. Switching
of load circuits is through relay contacts. Fan outputs can be
configured to operate 3, 2 or single speed fan motors. The fan control
also has configurations for user select fan speed with economy
function, continuous fan or auto cycle fan. This thermostat operates
on a single setpoint with automatic changeover from heating to cooling.
Installation Notice:
This high performance digital thermostat is designed to provide many
years of superior comfort control when properly installed and maintained.
To achieve maximum performance, this device is designed to draw
room air into itself continuously. Reasonable care must therefore be
taken with regard to air quality at the time of installation as well as
during periods of normal use, see operating conditions below.
Operating Conditions:
The electronic mechanisms incorporated within this unit REQUIRE
operating conditions similar to other electronic devices intended for
INDOOR USE ONLY, such as would be acceptable for TV and similar
household appliances. Relative humidity must be less than 95% and
the atmosphere must be non-condensing. For operation in bathrooms,
shower or pool areas, outdoor entry ways, greenhouses and similar
applications, order the
“-k”
option. This product includes protection
for coastal/tropical application, therefore it is suitable for use in high
humidity environments. Air quality must be maintained FREE of heavy
dust or debris which may infiltrate the interior of this device. Installation
in any space which is unfinished or undergoing repainting or general
rehabilitation is also considered product abuse. This device should be
removed from service during any local construction activity.
Cleaning:
This device incorporates a high impact polycarbonate enclosure which
is easily cleaned with a dry cloth or vacuum brush. Occasional soiling
may be cleaned with a soft cloth lightly dampened with water and/or
mild cleaning solution. IN NO CASE should this device be directly
sprayed with or exposed to free flowing liquids, including water, which
could penetrate its interior.
FAILURE TO OBSERVE ANY OF THE ABOVE CONDITIONS OF USE
WILL COMPLETELY VOID THE SUPPLIER WARRANTY.
CAUTION
MAKE SURE UNIT IS PROPERLY CONNECTED. DAMAGE TO THE
DIGITAL CONTROL CAN BE CAUSED BY MISWIRING, WHICH WILL
VOID THE WARRANTY. FOR SAFETY REASONS ALWAYS USE
WIRE NUTS ON ALL WIRE CONNECTIONS!!!
◦
+3V
SB1
SB2
COM
SEN3
SEN2
REF
+3V
SB1
SB2
COM
+3V
SB1
SB2
COM
◦
◦
Installation and Operating Instructions
Premier Series
24 Volt
PFC-M24
PFC-M24-RS
SETPOINT
AUTO
◦
◦
System Mode
Switch
HEAT/AUTO
/COO
L
°
F/°
C
PFC-A24
PFC-A24-RS
SETPOINT
AUTO
◦
◦
Decrease
temperature
Switches between
°F and °C
Selects
fan
function
Increase
temperature
°
F/°
C
4-PIPE FAN COIL, 2-PIPE ELECTRIC HEAT OR
ELECTRONIC AQUASTAT INSTALLATION:
This device should be installed and serviced by a qualified technician.
Junction box mounting is highly recommended.
1. Caution:
Make sure that power has been disconnected.
2.
All wiring must comply with applicable codes and ordinances.
3.
A thorough check-out of the system should be made after
installation is complete.
4.
If fan motor is larger than 1/4 HP and/or electric heaters are used
for heating, additional power relays will be required
5.
If retrofitting old thermostat, remove old thermostat from the
junction box, carefully noting the wire connections on the old unit.
Record wire color and terminal legends in spaces provided.
Disconnect old thermostat and remove any existing backplate or
mounting plate.
Old thermostat
wire function
Power Feed
Common
Heat
Cool
Low Fan
Medium Fan
High Fan
Cable
wire color
User Note: The top of this unit will become warm to the touch. This is a
normal operation. Internal heating is employed to continuously convect
air upward through the thermostat, thereby improving room air temperature
measurement. Direct conflict with a downward ceiling fan or system fan air
flow may result in false temperature reading. Locate thermostat to avoid
interference.
Screw: 6/32 x 3/4"
Mounting Bracket
Standard
Junction
Box
6.
Install the mounting bracket to the
junction box with the two long
mounting screws provided.
See mounting detail to the right.
Note:
If application involves a
double ganged junction box,
a backplate will be required for a
complete installation.
Please consult your supplier.
1
◦
SEN3
SEN2
REF
+3V
SB1
SB2
COM
◦
◦
◦