background image

2.          RECOMMENDED LOCATIONS OF ALARMS

2.1:   Heat alarms give an audible warning when the temperature at the alarm reaches 73°C. Heat alarms are ideal

for kitchens, garages, cellars, boiler rooms, attics and other areas where there are normally high levels of
fumes, smoke or dust which preclude the use of smoke alarms due to the risk of false alarms. For normalsized
bungalows, two-story houses, flats and maisonettes, the PSA recommends that the minimum level of protec-
tion should comprise smoke alarms in the hallways and staircases. This minimum standard necessitates one
smoke alarm in the hallway of a typical bungalow or one smoke alarm on each level of a two-story house.
Heat alarms should not be used in these circulation areas. If there are, for example, long hallways, even the
minimum standard may necessitate additional interconnected smoke alarms. If, however, the design of the
dwelling does not comply with modern fire safety standards, or if factors such as the presence of several
young children, elderly occupants or disabled people, or smokers, the use of portable heaters or solid fuel fires
during the night, or the use of electric blankets, particularly by the elderly, PSA advises that additional detec-
tion devices, installed within rooms, may be necessary. 

BEDROOM

 ATTIC

BEDROOM

HEAT ALARM

IONISATION SMOKE ALARM

 PHOTOELETRIC SMOKE ALARM 

KITCHEN

LIVING ROOM

GARAGE

UTILITY/

LAUNDRY

2.2:   The most favourable mounting location for a Heat

Alarm is on the ceiling and in the centre of the room.
At this location, the alarm  is closest to all areas

of  the room.    
EXCEPTION : When  the mounting  surface 
might  become considerably warmer or
cooler than the room, such as a poorly 
insulated ceiling, below  an unfinished attic,
or an exterior wall. In these cases the alarm 
should be mounted on an inside wall. 

2.1: If the alarm cannot be located in the centre 

of the room, an off-centre location can be 
used on the ceiling. When off-centre 
mounting an alarm on  the ceiling, locate it                               
at a minimum of 300mm  from the side wall (see diagram A)   

2.4: If a ceiling mounting location is not possible, the next logical location for mounting     

Heat Alarm is on the side wall. When mounting the alarm on the wall, use an inside 
wall with the top edge of the alarm at a minimum of 300mm and a maximum of 
600mm below the ceiling. (see diagram A)

Diagram A

2.5: When  mounting  the  alarm on a sloping
ceiling,  it  should  not  exceed  1500mm away
from the apex. The spacing of additional alarms, if
any,  should be based on a horizontal distance
measurement, not a measurement along the slope
of the ceiling (see diagram“B”)

Areas for 

Heat Alarms

Diagram B

1004-7201-01(HA240)_V2:_  2010.9.2  9:20 AM  Page 2

Содержание Lifesaver HA240

Страница 1: ... and or multiple station 24 units maximum The heat alarm is designed to activate at 73 C when the temperature range is between 58 C and 88 C Temperature rating 73 C 163 4 F Fixed temperature only Maximum ambient 88 C 190 4 F temperature at heat alarm Recommended coverage 230 square metres Note A Recommended spacing 15 3 metres Maximum distance from wall 7 6 metres Note B Note A Maximum coverage is...

Страница 2: ...alled within rooms may be necessary BEDROOM ATTIC BEDROOM HEAT ALARM IONISATION SMOKE ALARM PHOTOELETRIC SMOKE ALARM KITCHEN LIVING ROOM GARAGE UTILITY LAUNDRY 2 2 The most favourable mounting location for a Heat Alarm is on the ceiling and in the centre of the room At this location the alarm is closest to all areas of the room EXCEPTION When the mounting surface might become considerably warmer o...

Страница 3: ...ir conditioning near ceiling fans or other high air flow areas 3 2 In an area where the temperature may fall below 5 C 41 F or rise above 88 C 190 4 F 3 3 Near fluorescent lights electronic noise may cause nuisance alarms Diagram C 4 INSTALLATION INSTRUCTIONS PLEASE READ CAREFULLY 4 1 This Heat Alarm should be installed with an AS approved junction box All connections must be installed by a qualif...

Страница 4: ... in the AC connector into the back of the Heat Alarm Ensure the locks on the AC connector snaps firmly into place 6 5 Now mount the heat alarm onto the trim ring Rotate the heat alarm until the heat alarm snap firmly into place NOTE PLEASE ENSURE THAT BATTERY IS INSTALLED PRIOR TO MOUNTING OF HEAT ALARM Switch on the A C power and the green A C power ON indicator should be lit The Heat Alarm is no...

Страница 5: ...per second The rapid flashing LED and pulsating alarm will continue until the temperature drops below 73 C 163 4 F WHEN HEAT ALARMS ARE INTERCONNECTED with compatible Smoke Alarms only the Red LED of the originating unit will flash rapidly All other units in the interconnect system will sound an alarm but their Red LED s will not flash TESTING Test by pushing the test button on the cover and hold ...

Страница 6: ...your alarm by using a vacuum cleaner hose and vacuuming around the heat sensing element and the perimeter of the alarm The outside of the alarm can be wiped with a damp cloth We recommend a periodic monthly inspection and cleaning of the Heat Alarm to ensure proper operation AFTER CLEANING REINSTALL YOUR ALARM AND TEST YOUR ALARM BY USING THE TEST BUTTON AND CHECK THAT THE GREEN LED IS ON 12 LIMIT...

Страница 7: ...s defective in any way do not tamper with the unit Return it to PSA Products Pty Ltd 17 Millicent Street Burwood Victoria 3125 16 1 PSA Products Pty Ltd warrants that for two years from the date of purchase of the Heat Alarm it will re pair or replace the Heat Alarm at the option of PSA Products Pty Ltd due to any manufacturing defect at the cost of PSA Products Pty Ltd excluding any labour costs ...

Страница 8: ...et Burwood 3125 Victoria Australia Telephone 03 9888 9889 Facsimile 03 9888 9993 E mail enquiry psaproducts com au Website http www psaproducts com au AUSTRALIAN ELECTRICALAUTHORITY CS SGSE 100434 1004 7201 01 N10116 7 1004 7201 01 HA240 _V2 _ 2010 9 2 9 20 AM Page 8 ...

Отзывы: