Mounting Panel
Selecting Transformer
Remove the top cover and attach the panel to a wall close to
the unit using four #8 screws.
The VA rating of the transformer depends on the number of
actuators being used. The table below shows the VA required
for each zoning component including the ProR80J dampers.
The table below shows the number of dampers that can be
used with a 3 -zone installation using a 40, 60 or 75VA
transformer and ProR80J dampers.
Install the 24VAC transformer according to local electrical
codes and connect the 24VAC output to the terminals on the
panel using 2-conductor, 18 gage, thermostat wire as shown
below.
1.
3.
HVAC
PANEL
ZONE DAMPERS
1
1
2
2
3
FAD
3
THERMOST
ATS
Q
u
ic
k
V
ie
w
ProR321J Zoning Panel
ProZone
Two #8 screws
Two #8 screws
Panel
3-Zone
Maximum VA
40VA Transformer 60VA Transformer 75VA Transformer
10VA
11 Dampers
19 Dampers
26 Dampers
1.8VA
2.4VA
Typical VA
10VA
1.0VA
1.0VA
Zone Thermostat
Zone Damper
Line
24VAC
2-conductor, 18 gage
Thermostat Wire
3
Selecting Equipment
Jumper plugs are used to select the equipment type. The panel
is shipped with the jumper plugs in the Gas/Electric position. To
change equipment type, remove the jumper plug(s) and place
in the correct position as shown below. Use the PDMi3 to
change zone sizes, bypass options, fresh air control, staging
and much more.
2.
Jumper plug
GE
CHP
HP
DFHP
Gas/Electric selected.
GE
CHP
HP
DFHP
Conventional Heat Pump selected.
GE
CHP
Dual Fuel Heat Pump selected.
HP
DFHP