24
Figure 25 - Configuration Switch
8.0 Hardware Configuration
8.1 Configuration Switch
The Protégé® SE Integrated System Controller uses a 4 way dual in line dip switch located in the
centre of the PCB board. This switch is used to configure the boot up and power on settings for the
Protégé® SE Integrated System Controller. Each of the switch positions performs a different
function. For normal operation all of the switches should be in the off position.
Switch
Switch
Function
1
2
Power Up Boot Mode
OFF
OFF
Normal Operation
ON
OFF
BOOT Loader
OFF
ON
BIOS Utility
ON
ON
Reserved Do Not Set
Switch
Switch
Function
3
-
IP Address Configuration
OFF
-
Programmed IP Configuration
ON
-
IP Will be set to 192.168.111.222 while this switch remains on.
Allows the connection and review of the programmed IP address
or the modification to another setting.
Switch
Switch
Function
4
-
System Default
OFF
-
Normal Operation
ON
-
Factory Default Protégé® SE Integrated System Controller
BOOT MODE 1
BOOT MODE 2
BIOS COMMUNICATION
DEFAULT CONTROLLER
1
2
3
4
ON
OFF