5.4 Lock Output Connection
The Protégé® SE Integrated System Controller provides a connection for 2x electric strike
locks with
full monitoring of the lock circuit for tamper and over current/fuse blown conditions. The door lock
monitoring can be disabled if it is not required.
?
When using a door with an Entry and Exit Reader, the lock output should be
connected to Bell 1, and enable the swap lock option for the second reader input to
allow the reader LED’s to display the correct status.
!
Exceeding the maximum current on the controller outputs is not recommended.
Ensure the devices connected to the outputs are within the limits as detailed in the
Technical Specifications section on page 31.
!
As indicated in figure 19 the Lock Outputs are shared with the Bell/Siren functions.
You are able to select another output for the Lock Control (P3 or P4) if the
Bell/Siren function is required.
!
To use the lock outputs in conjunction with the Onboard Reader module the Lock
PGM for the Door associated with the Reader Port must be configured to be the
desired Lock Output on the Controller. By default this is not configured.
Figure 19 - Lock Output Connection
B1
+
B1-
B2
+
B2-
P3
P4
+
-
1N4007 Diode
12VDC Electric
Locking Device